How do I make this wiring inside cabinet safer? Announcing the arrival of Valued Associate #679: Cesar Manara Unicorn Meta Zoo #1: Why another podcast?How do I get power into my kitchen cabinet?Can I install junction boxes in a closet, and if so, what kind of box?Converting 120V undercabinet lighting to 12V strip lightingHow is ground wire handled on 240V outlet?Ok to conceal electrical junction box under cabinet behind removable toe-kickreplacing a range outletWiring Transition from Inside of wall to Outside of Wall for hard-wired applianceWhat is the proper way to bring this wire up to code and add an outlet?How to: Electrical Wiring Distance & Voltage Dropwiring - is this feeding other circuits or all switches?

Second order approximation of the loss function (Deep learning book, 7.33)

Is this homebrew racial feat, Stonehide, balanced?

How to open locks without disable device?

Do I need to protect SFP ports and optics from dust/contaminants? If so, how?

Can you stand up from being prone using Skirmisher outside of your turn?

How would I use different systems of magic when they are capable of the same effects?

How to not starve gigantic beasts

What is /etc/mtab in Linux?

Has a Nobel Peace laureate ever been accused of war crimes?

How do I check if a string is entirely made of the same substring?

Need of separate security plugins for both root and subfolder sites Wordpress?

Why isn't everyone flabbergasted about Bran's "gift"?

Does Feeblemind produce an ongoing magical effect that can be dispelled?

How to use @AuraEnabled base class method in Lightning Component?

Is it acceptable to use working hours to read general interest books?

What if Force was not Mass times Acceleration?

What to do with someone that cheated their way through university and a PhD program?

What's the difference between using dependency injection with a container and using a service locator?

PIC mathematical operations weird problem

Additive group of local rings

Implementing 3DES algorithm in Java: is my code secure?

Protagonist's race is hidden - should I reveal it?

The art of proof summarizing. Are there known rules, or is it a purely common sense matter?

What is the ongoing value of the Kanban board to the developers as opposed to management



How do I make this wiring inside cabinet safer?



Announcing the arrival of Valued Associate #679: Cesar Manara
Unicorn Meta Zoo #1: Why another podcast?How do I get power into my kitchen cabinet?Can I install junction boxes in a closet, and if so, what kind of box?Converting 120V undercabinet lighting to 12V strip lightingHow is ground wire handled on 240V outlet?Ok to conceal electrical junction box under cabinet behind removable toe-kickreplacing a range outletWiring Transition from Inside of wall to Outside of Wall for hard-wired applianceWhat is the proper way to bring this wire up to code and add an outlet?How to: Electrical Wiring Distance & Voltage Dropwiring - is this feeding other circuits or all switches?



.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty,.everyoneloves__bot-mid-leaderboard:empty margin-bottom:0;








13















tl;dr: How do I make this wiring meet code, or at least safer?



The pic below is inside one of my kitchen cabinets. Once upon a time the stove was located below these cabinets, and that wire must have run to an exhaust fan (note the metal vent in the pic). The stove had been moved to another spot by the time I bought the house, but the wire is still in the cabinet and still live.



When I bought the house the wire (old 2-wire NM, no ground) ran to a light fixture on the underside of the cabinet, but there was no junction box at all. Just exposed pigtails inside the cabinet. I'd like to improve things here, so what can I do, short of running a brand new wire with a ground through the wall? I figure putting the pigtails in an actual junction box would be a good place to start.



I plan on staying in the house for a few more years, so I'm more concerned with safety than exactly meeting code.



enter image description here










share|improve this question



















  • 1





    Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?

    – PhilippNagel
    Apr 17 at 19:37






  • 1





    @PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.

    – BradDaBug
    Apr 17 at 20:08











  • Are these wires controlled by a switch?

    – Freiheit
    Apr 18 at 16:59







  • 1





    Since there is no ground, DO NOT use a metal box!

    – Hot Licks
    Apr 18 at 21:30

















13















tl;dr: How do I make this wiring meet code, or at least safer?



The pic below is inside one of my kitchen cabinets. Once upon a time the stove was located below these cabinets, and that wire must have run to an exhaust fan (note the metal vent in the pic). The stove had been moved to another spot by the time I bought the house, but the wire is still in the cabinet and still live.



When I bought the house the wire (old 2-wire NM, no ground) ran to a light fixture on the underside of the cabinet, but there was no junction box at all. Just exposed pigtails inside the cabinet. I'd like to improve things here, so what can I do, short of running a brand new wire with a ground through the wall? I figure putting the pigtails in an actual junction box would be a good place to start.



I plan on staying in the house for a few more years, so I'm more concerned with safety than exactly meeting code.



enter image description here










share|improve this question



















  • 1





    Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?

    – PhilippNagel
    Apr 17 at 19:37






  • 1





    @PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.

    – BradDaBug
    Apr 17 at 20:08











  • Are these wires controlled by a switch?

    – Freiheit
    Apr 18 at 16:59







  • 1





    Since there is no ground, DO NOT use a metal box!

    – Hot Licks
    Apr 18 at 21:30













13












13








13


1






tl;dr: How do I make this wiring meet code, or at least safer?



The pic below is inside one of my kitchen cabinets. Once upon a time the stove was located below these cabinets, and that wire must have run to an exhaust fan (note the metal vent in the pic). The stove had been moved to another spot by the time I bought the house, but the wire is still in the cabinet and still live.



When I bought the house the wire (old 2-wire NM, no ground) ran to a light fixture on the underside of the cabinet, but there was no junction box at all. Just exposed pigtails inside the cabinet. I'd like to improve things here, so what can I do, short of running a brand new wire with a ground through the wall? I figure putting the pigtails in an actual junction box would be a good place to start.



I plan on staying in the house for a few more years, so I'm more concerned with safety than exactly meeting code.



enter image description here










share|improve this question
















tl;dr: How do I make this wiring meet code, or at least safer?



The pic below is inside one of my kitchen cabinets. Once upon a time the stove was located below these cabinets, and that wire must have run to an exhaust fan (note the metal vent in the pic). The stove had been moved to another spot by the time I bought the house, but the wire is still in the cabinet and still live.



When I bought the house the wire (old 2-wire NM, no ground) ran to a light fixture on the underside of the cabinet, but there was no junction box at all. Just exposed pigtails inside the cabinet. I'd like to improve things here, so what can I do, short of running a brand new wire with a ground through the wall? I figure putting the pigtails in an actual junction box would be a good place to start.



I plan on staying in the house for a few more years, so I'm more concerned with safety than exactly meeting code.



enter image description here







electrical wiring






share|improve this question















share|improve this question













share|improve this question




share|improve this question








edited Apr 18 at 13:52









Machavity

8,66322043




8,66322043










asked Apr 17 at 17:45









BradDaBugBradDaBug

16614




16614







  • 1





    Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?

    – PhilippNagel
    Apr 17 at 19:37






  • 1





    @PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.

    – BradDaBug
    Apr 17 at 20:08











  • Are these wires controlled by a switch?

    – Freiheit
    Apr 18 at 16:59







  • 1





    Since there is no ground, DO NOT use a metal box!

    – Hot Licks
    Apr 18 at 21:30












  • 1





    Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?

    – PhilippNagel
    Apr 17 at 19:37






  • 1





    @PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.

    – BradDaBug
    Apr 17 at 20:08











  • Are these wires controlled by a switch?

    – Freiheit
    Apr 18 at 16:59







  • 1





    Since there is no ground, DO NOT use a metal box!

    – Hot Licks
    Apr 18 at 21:30







1




1





Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?

– PhilippNagel
Apr 17 at 19:37





Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?

– PhilippNagel
Apr 17 at 19:37




1




1





@PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.

– BradDaBug
Apr 17 at 20:08





@PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.

– BradDaBug
Apr 17 at 20:08













Are these wires controlled by a switch?

– Freiheit
Apr 18 at 16:59






Are these wires controlled by a switch?

– Freiheit
Apr 18 at 16:59





1




1





Since there is no ground, DO NOT use a metal box!

– Hot Licks
Apr 18 at 21:30





Since there is no ground, DO NOT use a metal box!

– Hot Licks
Apr 18 at 21:30










5 Answers
5






active

oldest

votes


















13














There is nothing you can do with old wiring that doesn't meet code that will make it meet code. Old NM cable with no ground may have been "grandfathered" into an existing building, so long as you don't alter it. But that would not apply here because the WAY it was done was never per code.



Do you really need a circuit there? I would just find out where it comes from and disconnect it there, then pull it out. If you DO want another circuit there, you can attach new NM cable with a ground to the end of this before pulling it out, then get an "old work box" that can be mounted into the wall properly. An old work box is designed to go into a cut-out in the wall, then has "molly bolt" type fasteners that turn behind the wall and snug up against the back of it to hold the box in place (make sure you put the wire through the KO first!). Once the wire is in there, you can put in a receptacle for a light, fan etc.






share|improve this answer


















  • 6





    If it's stapled anywhere it probably won't pull.

    – J...
    Apr 17 at 23:22











  • True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!

    – J. Raefield
    Apr 18 at 0:26






  • 4





    Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.

    – J...
    Apr 18 at 0:38


















6














Sounds like you don't want the wire.



First figure out which breaker that circuit is on.



Turn off the breaker, see what other things go off. Put a harmonic tracer on the wire, find where it junctions and disconnect it there.



Typically fanhoods are on a circuit with other items. Once you have it disconnected in the box you could cut it back to the knock out and push it through so it could never be energized again then you could cut the wire in the cabinet back to where it penetrates the cabinet.



Or go with your plan put a box with a cover and wire nuts and leave it live.






share|improve this answer






























    5














    You may want to find what the local code says about such and follow it. I think just putting it "properly" in a metal box should be sufficient. Be sure the box is secure, the wires is clamped in the box and the caps are left on. As an extra measurement you could even cap them and then run electrical tape around them to ensure the caps won't fall off. Be sure to put a cover over the box when all done. Writing on the cover of what it is can't hurt either. If it is on its own circuit you could even turn the breaker off after this and label in the breaker as well.






    share|improve this answer


















    • 3





      DO NOT use a metal box if there is no ground!

      – Hot Licks
      Apr 18 at 21:29











    • @HotLicks username appropriate..

      – Alex M
      Apr 18 at 23:09


















    3














    Meeting your request for safety, and ranked best to worst:



    1. Trip and remove the breaker, replacing it with an appropriate position plug (other circuits may be on the breaker, preventing this).


    2. Disconnect the wire from wherever it goes (the breaker, an outlet, etc.) and pull it out (it may be stapled, preventing this).


    3. (After temporarily tripping breaker): Thread wire into a junction box with a stress-relief connector. Position the box as close to the hole in the wall as possible. Re-cap the wires, wrap with electrical tape. Screw to the wall and affix face plate.


    4. (After temporarily tripping breaker): Wrap a few turns around the wire nuts with electrical tape, then wrap the entire NM from where the outer insulation was stripped away to and including the wire nuts.


    As others have mentioned, there isn't a code-happy solution here. However, solutions (1)-(3) will pass a home inspection when you sell the home. (4) might not. It will depend on the inspector.






    share|improve this answer




















    • 2





      (4) is certain to alarm the inspector if you wrap with 'electrical wire' instead of electrical tape ;)

      – amI
      Apr 18 at 17:56






    • 1





      @amI THANK YOU! Imperfection is sooo inconvenient. :-)

      – JBH
      Apr 18 at 19:32


















    0














    Trace these wires back to where they are spliced on the branched and disconnect. Remove if possible and plug holes at boxes or panels where this wire ran.






    share|improve this answer























      Your Answer








      StackExchange.ready(function()
      var channelOptions =
      tags: "".split(" "),
      id: "73"
      ;
      initTagRenderer("".split(" "), "".split(" "), channelOptions);

      StackExchange.using("externalEditor", function()
      // Have to fire editor after snippets, if snippets enabled
      if (StackExchange.settings.snippets.snippetsEnabled)
      StackExchange.using("snippets", function()
      createEditor();
      );

      else
      createEditor();

      );

      function createEditor()
      StackExchange.prepareEditor(
      heartbeatType: 'answer',
      autoActivateHeartbeat: false,
      convertImagesToLinks: false,
      noModals: true,
      showLowRepImageUploadWarning: true,
      reputationToPostImages: null,
      bindNavPrevention: true,
      postfix: "",
      imageUploader:
      brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
      contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
      allowUrls: true
      ,
      noCode: true, onDemand: true,
      discardSelector: ".discard-answer"
      ,immediatelyShowMarkdownHelp:true
      );



      );













      draft saved

      draft discarded


















      StackExchange.ready(
      function ()
      StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f162263%2fhow-do-i-make-this-wiring-inside-cabinet-safer%23new-answer', 'question_page');

      );

      Post as a guest















      Required, but never shown

























      5 Answers
      5






      active

      oldest

      votes








      5 Answers
      5






      active

      oldest

      votes









      active

      oldest

      votes






      active

      oldest

      votes









      13














      There is nothing you can do with old wiring that doesn't meet code that will make it meet code. Old NM cable with no ground may have been "grandfathered" into an existing building, so long as you don't alter it. But that would not apply here because the WAY it was done was never per code.



      Do you really need a circuit there? I would just find out where it comes from and disconnect it there, then pull it out. If you DO want another circuit there, you can attach new NM cable with a ground to the end of this before pulling it out, then get an "old work box" that can be mounted into the wall properly. An old work box is designed to go into a cut-out in the wall, then has "molly bolt" type fasteners that turn behind the wall and snug up against the back of it to hold the box in place (make sure you put the wire through the KO first!). Once the wire is in there, you can put in a receptacle for a light, fan etc.






      share|improve this answer


















      • 6





        If it's stapled anywhere it probably won't pull.

        – J...
        Apr 17 at 23:22











      • True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!

        – J. Raefield
        Apr 18 at 0:26






      • 4





        Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.

        – J...
        Apr 18 at 0:38















      13














      There is nothing you can do with old wiring that doesn't meet code that will make it meet code. Old NM cable with no ground may have been "grandfathered" into an existing building, so long as you don't alter it. But that would not apply here because the WAY it was done was never per code.



      Do you really need a circuit there? I would just find out where it comes from and disconnect it there, then pull it out. If you DO want another circuit there, you can attach new NM cable with a ground to the end of this before pulling it out, then get an "old work box" that can be mounted into the wall properly. An old work box is designed to go into a cut-out in the wall, then has "molly bolt" type fasteners that turn behind the wall and snug up against the back of it to hold the box in place (make sure you put the wire through the KO first!). Once the wire is in there, you can put in a receptacle for a light, fan etc.






      share|improve this answer


















      • 6





        If it's stapled anywhere it probably won't pull.

        – J...
        Apr 17 at 23:22











      • True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!

        – J. Raefield
        Apr 18 at 0:26






      • 4





        Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.

        – J...
        Apr 18 at 0:38













      13












      13








      13







      There is nothing you can do with old wiring that doesn't meet code that will make it meet code. Old NM cable with no ground may have been "grandfathered" into an existing building, so long as you don't alter it. But that would not apply here because the WAY it was done was never per code.



      Do you really need a circuit there? I would just find out where it comes from and disconnect it there, then pull it out. If you DO want another circuit there, you can attach new NM cable with a ground to the end of this before pulling it out, then get an "old work box" that can be mounted into the wall properly. An old work box is designed to go into a cut-out in the wall, then has "molly bolt" type fasteners that turn behind the wall and snug up against the back of it to hold the box in place (make sure you put the wire through the KO first!). Once the wire is in there, you can put in a receptacle for a light, fan etc.






      share|improve this answer













      There is nothing you can do with old wiring that doesn't meet code that will make it meet code. Old NM cable with no ground may have been "grandfathered" into an existing building, so long as you don't alter it. But that would not apply here because the WAY it was done was never per code.



      Do you really need a circuit there? I would just find out where it comes from and disconnect it there, then pull it out. If you DO want another circuit there, you can attach new NM cable with a ground to the end of this before pulling it out, then get an "old work box" that can be mounted into the wall properly. An old work box is designed to go into a cut-out in the wall, then has "molly bolt" type fasteners that turn behind the wall and snug up against the back of it to hold the box in place (make sure you put the wire through the KO first!). Once the wire is in there, you can put in a receptacle for a light, fan etc.







      share|improve this answer












      share|improve this answer



      share|improve this answer










      answered Apr 17 at 18:03









      J. RaefieldJ. Raefield

      4,142211




      4,142211







      • 6





        If it's stapled anywhere it probably won't pull.

        – J...
        Apr 17 at 23:22











      • True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!

        – J. Raefield
        Apr 18 at 0:26






      • 4





        Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.

        – J...
        Apr 18 at 0:38












      • 6





        If it's stapled anywhere it probably won't pull.

        – J...
        Apr 17 at 23:22











      • True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!

        – J. Raefield
        Apr 18 at 0:26






      • 4





        Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.

        – J...
        Apr 18 at 0:38







      6




      6





      If it's stapled anywhere it probably won't pull.

      – J...
      Apr 17 at 23:22





      If it's stapled anywhere it probably won't pull.

      – J...
      Apr 17 at 23:22













      True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!

      – J. Raefield
      Apr 18 at 0:26





      True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!

      – J. Raefield
      Apr 18 at 0:26




      4




      4





      Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.

      – J...
      Apr 18 at 0:38





      Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.

      – J...
      Apr 18 at 0:38













      6














      Sounds like you don't want the wire.



      First figure out which breaker that circuit is on.



      Turn off the breaker, see what other things go off. Put a harmonic tracer on the wire, find where it junctions and disconnect it there.



      Typically fanhoods are on a circuit with other items. Once you have it disconnected in the box you could cut it back to the knock out and push it through so it could never be energized again then you could cut the wire in the cabinet back to where it penetrates the cabinet.



      Or go with your plan put a box with a cover and wire nuts and leave it live.






      share|improve this answer



























        6














        Sounds like you don't want the wire.



        First figure out which breaker that circuit is on.



        Turn off the breaker, see what other things go off. Put a harmonic tracer on the wire, find where it junctions and disconnect it there.



        Typically fanhoods are on a circuit with other items. Once you have it disconnected in the box you could cut it back to the knock out and push it through so it could never be energized again then you could cut the wire in the cabinet back to where it penetrates the cabinet.



        Or go with your plan put a box with a cover and wire nuts and leave it live.






        share|improve this answer

























          6












          6








          6







          Sounds like you don't want the wire.



          First figure out which breaker that circuit is on.



          Turn off the breaker, see what other things go off. Put a harmonic tracer on the wire, find where it junctions and disconnect it there.



          Typically fanhoods are on a circuit with other items. Once you have it disconnected in the box you could cut it back to the knock out and push it through so it could never be energized again then you could cut the wire in the cabinet back to where it penetrates the cabinet.



          Or go with your plan put a box with a cover and wire nuts and leave it live.






          share|improve this answer













          Sounds like you don't want the wire.



          First figure out which breaker that circuit is on.



          Turn off the breaker, see what other things go off. Put a harmonic tracer on the wire, find where it junctions and disconnect it there.



          Typically fanhoods are on a circuit with other items. Once you have it disconnected in the box you could cut it back to the knock out and push it through so it could never be energized again then you could cut the wire in the cabinet back to where it penetrates the cabinet.



          Or go with your plan put a box with a cover and wire nuts and leave it live.







          share|improve this answer












          share|improve this answer



          share|improve this answer










          answered Apr 17 at 19:01









          Fresh CodemongerFresh Codemonger

          5667




          5667





















              5














              You may want to find what the local code says about such and follow it. I think just putting it "properly" in a metal box should be sufficient. Be sure the box is secure, the wires is clamped in the box and the caps are left on. As an extra measurement you could even cap them and then run electrical tape around them to ensure the caps won't fall off. Be sure to put a cover over the box when all done. Writing on the cover of what it is can't hurt either. If it is on its own circuit you could even turn the breaker off after this and label in the breaker as well.






              share|improve this answer


















              • 3





                DO NOT use a metal box if there is no ground!

                – Hot Licks
                Apr 18 at 21:29











              • @HotLicks username appropriate..

                – Alex M
                Apr 18 at 23:09















              5














              You may want to find what the local code says about such and follow it. I think just putting it "properly" in a metal box should be sufficient. Be sure the box is secure, the wires is clamped in the box and the caps are left on. As an extra measurement you could even cap them and then run electrical tape around them to ensure the caps won't fall off. Be sure to put a cover over the box when all done. Writing on the cover of what it is can't hurt either. If it is on its own circuit you could even turn the breaker off after this and label in the breaker as well.






              share|improve this answer


















              • 3





                DO NOT use a metal box if there is no ground!

                – Hot Licks
                Apr 18 at 21:29











              • @HotLicks username appropriate..

                – Alex M
                Apr 18 at 23:09













              5












              5








              5







              You may want to find what the local code says about such and follow it. I think just putting it "properly" in a metal box should be sufficient. Be sure the box is secure, the wires is clamped in the box and the caps are left on. As an extra measurement you could even cap them and then run electrical tape around them to ensure the caps won't fall off. Be sure to put a cover over the box when all done. Writing on the cover of what it is can't hurt either. If it is on its own circuit you could even turn the breaker off after this and label in the breaker as well.






              share|improve this answer













              You may want to find what the local code says about such and follow it. I think just putting it "properly" in a metal box should be sufficient. Be sure the box is secure, the wires is clamped in the box and the caps are left on. As an extra measurement you could even cap them and then run electrical tape around them to ensure the caps won't fall off. Be sure to put a cover over the box when all done. Writing on the cover of what it is can't hurt either. If it is on its own circuit you could even turn the breaker off after this and label in the breaker as well.







              share|improve this answer












              share|improve this answer



              share|improve this answer










              answered Apr 17 at 19:24









              Micah MontoyaMicah Montoya

              61926




              61926







              • 3





                DO NOT use a metal box if there is no ground!

                – Hot Licks
                Apr 18 at 21:29











              • @HotLicks username appropriate..

                – Alex M
                Apr 18 at 23:09












              • 3





                DO NOT use a metal box if there is no ground!

                – Hot Licks
                Apr 18 at 21:29











              • @HotLicks username appropriate..

                – Alex M
                Apr 18 at 23:09







              3




              3





              DO NOT use a metal box if there is no ground!

              – Hot Licks
              Apr 18 at 21:29





              DO NOT use a metal box if there is no ground!

              – Hot Licks
              Apr 18 at 21:29













              @HotLicks username appropriate..

              – Alex M
              Apr 18 at 23:09





              @HotLicks username appropriate..

              – Alex M
              Apr 18 at 23:09











              3














              Meeting your request for safety, and ranked best to worst:



              1. Trip and remove the breaker, replacing it with an appropriate position plug (other circuits may be on the breaker, preventing this).


              2. Disconnect the wire from wherever it goes (the breaker, an outlet, etc.) and pull it out (it may be stapled, preventing this).


              3. (After temporarily tripping breaker): Thread wire into a junction box with a stress-relief connector. Position the box as close to the hole in the wall as possible. Re-cap the wires, wrap with electrical tape. Screw to the wall and affix face plate.


              4. (After temporarily tripping breaker): Wrap a few turns around the wire nuts with electrical tape, then wrap the entire NM from where the outer insulation was stripped away to and including the wire nuts.


              As others have mentioned, there isn't a code-happy solution here. However, solutions (1)-(3) will pass a home inspection when you sell the home. (4) might not. It will depend on the inspector.






              share|improve this answer




















              • 2





                (4) is certain to alarm the inspector if you wrap with 'electrical wire' instead of electrical tape ;)

                – amI
                Apr 18 at 17:56






              • 1





                @amI THANK YOU! Imperfection is sooo inconvenient. :-)

                – JBH
                Apr 18 at 19:32















              3














              Meeting your request for safety, and ranked best to worst:



              1. Trip and remove the breaker, replacing it with an appropriate position plug (other circuits may be on the breaker, preventing this).


              2. Disconnect the wire from wherever it goes (the breaker, an outlet, etc.) and pull it out (it may be stapled, preventing this).


              3. (After temporarily tripping breaker): Thread wire into a junction box with a stress-relief connector. Position the box as close to the hole in the wall as possible. Re-cap the wires, wrap with electrical tape. Screw to the wall and affix face plate.


              4. (After temporarily tripping breaker): Wrap a few turns around the wire nuts with electrical tape, then wrap the entire NM from where the outer insulation was stripped away to and including the wire nuts.


              As others have mentioned, there isn't a code-happy solution here. However, solutions (1)-(3) will pass a home inspection when you sell the home. (4) might not. It will depend on the inspector.






              share|improve this answer




















              • 2





                (4) is certain to alarm the inspector if you wrap with 'electrical wire' instead of electrical tape ;)

                – amI
                Apr 18 at 17:56






              • 1





                @amI THANK YOU! Imperfection is sooo inconvenient. :-)

                – JBH
                Apr 18 at 19:32













              3












              3








              3







              Meeting your request for safety, and ranked best to worst:



              1. Trip and remove the breaker, replacing it with an appropriate position plug (other circuits may be on the breaker, preventing this).


              2. Disconnect the wire from wherever it goes (the breaker, an outlet, etc.) and pull it out (it may be stapled, preventing this).


              3. (After temporarily tripping breaker): Thread wire into a junction box with a stress-relief connector. Position the box as close to the hole in the wall as possible. Re-cap the wires, wrap with electrical tape. Screw to the wall and affix face plate.


              4. (After temporarily tripping breaker): Wrap a few turns around the wire nuts with electrical tape, then wrap the entire NM from where the outer insulation was stripped away to and including the wire nuts.


              As others have mentioned, there isn't a code-happy solution here. However, solutions (1)-(3) will pass a home inspection when you sell the home. (4) might not. It will depend on the inspector.






              share|improve this answer















              Meeting your request for safety, and ranked best to worst:



              1. Trip and remove the breaker, replacing it with an appropriate position plug (other circuits may be on the breaker, preventing this).


              2. Disconnect the wire from wherever it goes (the breaker, an outlet, etc.) and pull it out (it may be stapled, preventing this).


              3. (After temporarily tripping breaker): Thread wire into a junction box with a stress-relief connector. Position the box as close to the hole in the wall as possible. Re-cap the wires, wrap with electrical tape. Screw to the wall and affix face plate.


              4. (After temporarily tripping breaker): Wrap a few turns around the wire nuts with electrical tape, then wrap the entire NM from where the outer insulation was stripped away to and including the wire nuts.


              As others have mentioned, there isn't a code-happy solution here. However, solutions (1)-(3) will pass a home inspection when you sell the home. (4) might not. It will depend on the inspector.







              share|improve this answer














              share|improve this answer



              share|improve this answer








              edited Apr 18 at 19:31

























              answered Apr 18 at 4:48









              JBHJBH

              28529




              28529







              • 2





                (4) is certain to alarm the inspector if you wrap with 'electrical wire' instead of electrical tape ;)

                – amI
                Apr 18 at 17:56






              • 1





                @amI THANK YOU! Imperfection is sooo inconvenient. :-)

                – JBH
                Apr 18 at 19:32












              • 2





                (4) is certain to alarm the inspector if you wrap with 'electrical wire' instead of electrical tape ;)

                – amI
                Apr 18 at 17:56






              • 1





                @amI THANK YOU! Imperfection is sooo inconvenient. :-)

                – JBH
                Apr 18 at 19:32







              2




              2





              (4) is certain to alarm the inspector if you wrap with 'electrical wire' instead of electrical tape ;)

              – amI
              Apr 18 at 17:56





              (4) is certain to alarm the inspector if you wrap with 'electrical wire' instead of electrical tape ;)

              – amI
              Apr 18 at 17:56




              1




              1





              @amI THANK YOU! Imperfection is sooo inconvenient. :-)

              – JBH
              Apr 18 at 19:32





              @amI THANK YOU! Imperfection is sooo inconvenient. :-)

              – JBH
              Apr 18 at 19:32











              0














              Trace these wires back to where they are spliced on the branched and disconnect. Remove if possible and plug holes at boxes or panels where this wire ran.






              share|improve this answer



























                0














                Trace these wires back to where they are spliced on the branched and disconnect. Remove if possible and plug holes at boxes or panels where this wire ran.






                share|improve this answer

























                  0












                  0








                  0







                  Trace these wires back to where they are spliced on the branched and disconnect. Remove if possible and plug holes at boxes or panels where this wire ran.






                  share|improve this answer













                  Trace these wires back to where they are spliced on the branched and disconnect. Remove if possible and plug holes at boxes or panels where this wire ran.







                  share|improve this answer












                  share|improve this answer



                  share|improve this answer










                  answered Apr 18 at 9:56









                  GeraldGerald

                  271




                  271



























                      draft saved

                      draft discarded
















































                      Thanks for contributing an answer to Home Improvement Stack Exchange!


                      • Please be sure to answer the question. Provide details and share your research!

                      But avoid


                      • Asking for help, clarification, or responding to other answers.

                      • Making statements based on opinion; back them up with references or personal experience.

                      To learn more, see our tips on writing great answers.




                      draft saved


                      draft discarded














                      StackExchange.ready(
                      function ()
                      StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f162263%2fhow-do-i-make-this-wiring-inside-cabinet-safer%23new-answer', 'question_page');

                      );

                      Post as a guest















                      Required, but never shown





















































                      Required, but never shown














                      Required, but never shown












                      Required, but never shown







                      Required, but never shown

































                      Required, but never shown














                      Required, but never shown












                      Required, but never shown







                      Required, but never shown







                      Popular posts from this blog

                      Wikipedia:Vital articles Мазмуну Biography - Өмүр баян Philosophy and psychology - Философия жана психология Religion - Дин Social sciences - Коомдук илимдер Language and literature - Тил жана адабият Science - Илим Technology - Технология Arts and recreation - Искусство жана эс алуу History and geography - Тарых жана география Навигация менюсу

                      Bruxelas-Capital Índice Historia | Composición | Situación lingüística | Clima | Cidades irmandadas | Notas | Véxase tamén | Menú de navegacióneO uso das linguas en Bruxelas e a situación do neerlandés"Rexión de Bruxelas Capital"o orixinalSitio da rexiónPáxina de Bruselas no sitio da Oficina de Promoción Turística de Valonia e BruxelasMapa Interactivo da Rexión de Bruxelas-CapitaleeWorldCat332144929079854441105155190212ID28008674080552-90000 0001 0666 3698n94104302ID540940339365017018237

                      What should I write in an apology letter, since I have decided not to join a company after accepting an offer letterShould I keep looking after accepting a job offer?What should I do when I've been verbally told I would get an offer letter, but still haven't gotten one after 4 weeks?Do I accept an offer from a company that I am not likely to join?New job hasn't confirmed starting date and I want to give current employer as much notice as possibleHow should I address my manager in my resignation letter?HR delayed background verification, now jobless as resignedNo email communication after accepting a formal written offer. How should I phrase the call?What should I do if after receiving a verbal offer letter I am informed that my written job offer is put on hold due to some internal issues?Should I inform the current employer that I am about to resign within 1-2 weeks since I have signed the offer letter and waiting for visa?What company will do, if I send their offer letter to another company