Does the neutral wire have any voltage?How do remaining two phases act as return path in three phase systemHow to find Voltage based on reference nodes?Why is using a single phase device across phases of a 3 phase outlet OK?Three phase heaters and ampsHow to calculate the neutral wire size of a home (department)?What are the adavantages of neutral vs. isolated grounding?Grounding conductor has a non-zero voltage (i.e. with respect to “true” ground). Why?Why isn't line to line voltage zero?3 phase generator residual voltageHow does circuit completes when physical ground(earth) is used as neutral?How are the individual homes connected in a 3 phase power distribution system (power grid) so that they have correct voltage?Why is earth at 0 V with respect to phase?
Why is the marginal distribution/marginal probability described as "marginal"?
Does a non-singular matrix have a large minor with disjoint rows and columns and full rank?
Holding rent money for my friend which amounts to over $10k?
Why does string strummed with finger sound different from the one strummed with pick?
He is the first man to arrive here
How can I safely determine the output voltage and current of a transformer?
Non-African Click Languages
Why did the soldiers of the North disobey Jon?
Do high-wing aircraft represent more difficult engineering challenges than low-wing aircraft?
I recently started my machine learning PhD and I have absolutely no idea what I'm doing
Is it standard for US-based universities to consider the ethnicity of an applicant during PhD admissions?
Canadian citizen who is presently in litigation with a US-based company
How to generate a triangular grid from a list of points
Would it be fair to use 1d30 (instead of rolling 2d20 and taking the higher die) for advantage rolls?
Why are lawsuits between the President and Congress not automatically sent to the Supreme Court
How can we delete item permanently without storing in Recycle Bin?
Promotion comes with unexpected 24/7/365 on-call
Is there an academic word that means "to split hairs over"?
AD: OU for system administrator accounts
What technology would Dwarves need to forge titanium?
Why aren't satellites disintegrated even though they orbit earth within their Roche Limits?
Why is Drogon so much better in battle than Rhaegal and Viserion?
multiline equation inside a matrix that is a part of multiline equation
Is Precocious Apprentice enough for Mystic Theurge?
Does the neutral wire have any voltage?
How do remaining two phases act as return path in three phase systemHow to find Voltage based on reference nodes?Why is using a single phase device across phases of a 3 phase outlet OK?Three phase heaters and ampsHow to calculate the neutral wire size of a home (department)?What are the adavantages of neutral vs. isolated grounding?Grounding conductor has a non-zero voltage (i.e. with respect to “true” ground). Why?Why isn't line to line voltage zero?3 phase generator residual voltageHow does circuit completes when physical ground(earth) is used as neutral?How are the individual homes connected in a 3 phase power distribution system (power grid) so that they have correct voltage?Why is earth at 0 V with respect to phase?
.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty,.everyoneloves__bot-mid-leaderboard:empty margin-bottom:0;
$begingroup$
In this article, the author talks about 3 phase and the magic of a missing neutral wire. And there's the following paragraph:
In a 3-phase system the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact). If your X-N (and Y-N and Z-N) voltage is 120V (common in the US), the X-Y (and Y-Z and Z-X) voltages (a.k.a. “cross-phase” voltages) will be 120V * 1.73 = 208V.
When he says the X-N voltage is 120V, with N being the reference voltage, is the reference voltage 0V or does it have some value?
From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?
power-supply power wire three-phase neutral
$endgroup$
|
show 3 more comments
$begingroup$
In this article, the author talks about 3 phase and the magic of a missing neutral wire. And there's the following paragraph:
In a 3-phase system the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact). If your X-N (and Y-N and Z-N) voltage is 120V (common in the US), the X-Y (and Y-Z and Z-X) voltages (a.k.a. “cross-phase” voltages) will be 120V * 1.73 = 208V.
When he says the X-N voltage is 120V, with N being the reference voltage, is the reference voltage 0V or does it have some value?
From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?
power-supply power wire three-phase neutral
$endgroup$
4
$begingroup$
I think you're not understanding something here. There is no absolute value of voltage, just voltage differences.
$endgroup$
– Hearth
May 5 at 12:43
$begingroup$
No I did understand that part. I'm saying the 120V voltage difference between X-N can be either 121-1 or 120-0. Which one is it?
$endgroup$
– noorav
May 5 at 12:45
6
$begingroup$
The fact that you're asking that shows that you don't understand.
$endgroup$
– Hearth
May 5 at 12:46
$begingroup$
I'm sorry, but where is my understanding flawed? This is how I've been learning about voltage difference for so long. Could you please correct me
$endgroup$
– noorav
May 5 at 12:47
3
$begingroup$
Well, you're asking whether there's a voltage on the neutral wire. A voltage relative to what?
$endgroup$
– Hearth
May 5 at 12:49
|
show 3 more comments
$begingroup$
In this article, the author talks about 3 phase and the magic of a missing neutral wire. And there's the following paragraph:
In a 3-phase system the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact). If your X-N (and Y-N and Z-N) voltage is 120V (common in the US), the X-Y (and Y-Z and Z-X) voltages (a.k.a. “cross-phase” voltages) will be 120V * 1.73 = 208V.
When he says the X-N voltage is 120V, with N being the reference voltage, is the reference voltage 0V or does it have some value?
From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?
power-supply power wire three-phase neutral
$endgroup$
In this article, the author talks about 3 phase and the magic of a missing neutral wire. And there's the following paragraph:
In a 3-phase system the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact). If your X-N (and Y-N and Z-N) voltage is 120V (common in the US), the X-Y (and Y-Z and Z-X) voltages (a.k.a. “cross-phase” voltages) will be 120V * 1.73 = 208V.
When he says the X-N voltage is 120V, with N being the reference voltage, is the reference voltage 0V or does it have some value?
From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?
power-supply power wire three-phase neutral
power-supply power wire three-phase neutral
edited May 5 at 12:45
JRE
25.4k64585
25.4k64585
asked May 5 at 12:41
nooravnoorav
807
807
4
$begingroup$
I think you're not understanding something here. There is no absolute value of voltage, just voltage differences.
$endgroup$
– Hearth
May 5 at 12:43
$begingroup$
No I did understand that part. I'm saying the 120V voltage difference between X-N can be either 121-1 or 120-0. Which one is it?
$endgroup$
– noorav
May 5 at 12:45
6
$begingroup$
The fact that you're asking that shows that you don't understand.
$endgroup$
– Hearth
May 5 at 12:46
$begingroup$
I'm sorry, but where is my understanding flawed? This is how I've been learning about voltage difference for so long. Could you please correct me
$endgroup$
– noorav
May 5 at 12:47
3
$begingroup$
Well, you're asking whether there's a voltage on the neutral wire. A voltage relative to what?
$endgroup$
– Hearth
May 5 at 12:49
|
show 3 more comments
4
$begingroup$
I think you're not understanding something here. There is no absolute value of voltage, just voltage differences.
$endgroup$
– Hearth
May 5 at 12:43
$begingroup$
No I did understand that part. I'm saying the 120V voltage difference between X-N can be either 121-1 or 120-0. Which one is it?
$endgroup$
– noorav
May 5 at 12:45
6
$begingroup$
The fact that you're asking that shows that you don't understand.
$endgroup$
– Hearth
May 5 at 12:46
$begingroup$
I'm sorry, but where is my understanding flawed? This is how I've been learning about voltage difference for so long. Could you please correct me
$endgroup$
– noorav
May 5 at 12:47
3
$begingroup$
Well, you're asking whether there's a voltage on the neutral wire. A voltage relative to what?
$endgroup$
– Hearth
May 5 at 12:49
4
4
$begingroup$
I think you're not understanding something here. There is no absolute value of voltage, just voltage differences.
$endgroup$
– Hearth
May 5 at 12:43
$begingroup$
I think you're not understanding something here. There is no absolute value of voltage, just voltage differences.
$endgroup$
– Hearth
May 5 at 12:43
$begingroup$
No I did understand that part. I'm saying the 120V voltage difference between X-N can be either 121-1 or 120-0. Which one is it?
$endgroup$
– noorav
May 5 at 12:45
$begingroup$
No I did understand that part. I'm saying the 120V voltage difference between X-N can be either 121-1 or 120-0. Which one is it?
$endgroup$
– noorav
May 5 at 12:45
6
6
$begingroup$
The fact that you're asking that shows that you don't understand.
$endgroup$
– Hearth
May 5 at 12:46
$begingroup$
The fact that you're asking that shows that you don't understand.
$endgroup$
– Hearth
May 5 at 12:46
$begingroup$
I'm sorry, but where is my understanding flawed? This is how I've been learning about voltage difference for so long. Could you please correct me
$endgroup$
– noorav
May 5 at 12:47
$begingroup$
I'm sorry, but where is my understanding flawed? This is how I've been learning about voltage difference for so long. Could you please correct me
$endgroup$
– noorav
May 5 at 12:47
3
3
$begingroup$
Well, you're asking whether there's a voltage on the neutral wire. A voltage relative to what?
$endgroup$
– Hearth
May 5 at 12:49
$begingroup$
Well, you're asking whether there's a voltage on the neutral wire. A voltage relative to what?
$endgroup$
– Hearth
May 5 at 12:49
|
show 3 more comments
4 Answers
4
active
oldest
votes
$begingroup$
The neutral wire is defined to be 0V. And each phase individually has a voltage relative to neutral of 115V if you are in the US, and 230V if you are in most of Europe.
But because the three phases are 120 deg out of phase compared to each other this results in a voltage difference of 115V * sqrt(3) = 200V (or 230V * sqrt(3) = 400V) between any two phases.
Depending on the type of mains distribution system you've got in the country you live (I don't know how it is in the US) the neutral wire might be connected to earth at the power company. Keep in mind however, that even though the neutral wire might be connected to earth, this doesn't mean that it is actually at earth potential, because a return current might be flowing in the neutral wire, and due to the resistance in the wire this will cause a voltage at your end of the neutral wire.
It is also important to keep in mind that in many countries the mains plugs we use can actually be turned 180 deg putting line where neutral was supposed to be, meaning that with these kinds of systems you can never be sure if your neutral is actually neutral or line (BE CAREFUL!)
So to sum it up: The neutral wire is defined to be 0V. But will typically be at some voltage potential (relative to earth).
$endgroup$
1
$begingroup$
Sometimes, earth is defined to be zero volts instead of neutral. Though they're nominally the same, they can differ. This can be important, and I feel like it ought to be mentioned at least.
$endgroup$
– Hearth
May 5 at 16:21
add a comment |
$begingroup$
The original article you've quoted is garbled.
... the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact).
It can't be three times higher and $ sqrt 3$ times higher simultaneously. The correct value is $ sqrt 3$ times higher.
Figure 1. The diagram in question. Source: PacketPower.
When he says the X-N voltage is 120 V, with N being the reference voltage, is the reference voltage 0 V or does it have some value?
The reference is the wye (star) point where the three windings share a common node. In this diagram it is neutralised by connecting to Earth. (That means that this conductor should not see any significant voltage on it with respect to earth.) There will be 120 V between each of the phases and the wye point whether it is earthed or not.
From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?
It depends on local regulations. If we're dealing with a transformer secondary here then typically the primary will be delta powered so there may be no neutral on the incoming supply. The solution is to ground the wye to the building's earth bonding in which case it would be the same as earth grounding. In the case of a ship, for example, the "earth" would be the ship's hull.
Figure 2. A delta-wye (delta-star) transformer connection. Source: Gamatronic.
Here we can see that there is no neutral connection on the incoming supply. Using a wye configuration on the secondary allows us to create one for internal use. The wye point can be left floating or can be grounded.
$endgroup$
$begingroup$
"Here we can see that there is no neutral connection on the incoming supply." So what provides the return path for flow of current?
$endgroup$
– noorav
May 5 at 13:53
$begingroup$
The other two phases. See my answer to How do remaining two phases act as return path in three phase system?
$endgroup$
– Transistor
May 5 at 14:21
add a comment |
$begingroup$
The neutral wire is grounded, so if you literally took a multi-meter and tried to read voltage between the neutral wire and ground, you will read 0 voltage. Please note, this is for a healthy working balanced system.
So yes, consider the neutral wire 0V if everything is in working order.
$endgroup$
$begingroup$
That depends completely on the type of distribution system is used in the country you live in. In most of Europe the neutral is indeed connected to earth at the power company, but this is not always the case/ not the case in all countries..
$endgroup$
– Vinzent
May 5 at 13:02
$begingroup$
Do you have an example where someone is running power through the neutral wire? Would be interesting to see this setup.
$endgroup$
– Busta
May 5 at 13:05
1
$begingroup$
You can read this wiki page about earthing systems: en.wikipedia.org/wiki/Earthing_system, It describes the different types of earthing systems, such as TN, TT, IN and IT..
$endgroup$
– Vinzent
May 5 at 13:10
$begingroup$
Thanks for the link. So I will default that my answer works in traditional WYE (Star) / Delta systems that use a 4-wire 3-phase traditional set-up where the neutral is tied to the ground. Hence, if you tried to read voltage between neutral and ground...theoretically you should get 0volts but your answer explained why you may see some voltage.. The original question gave the assumption that the neutral wire is grounded.
$endgroup$
– Busta
May 5 at 13:18
add a comment |
$begingroup$
"Here we can see that there is no neutral connection on the incoming supply."
So what provides the return path for flow of current?
This was asked as a comment, but to answer it I need far more space than a comment allows.
With a simple two wire AC connection, the outgoing current on the hot wire is has the exact same absolute magnitude as the return current in the neutral wire, but they have opposite signs. In addition to this, the current is actually a sine wave.
Now, lets take three copies of this, but adjust the phase of two of the circuits so that all three are 120 degrees out of phase with respect to each other.
Next, lets replace the three neutral wires with one big wire three times the capacity. Up to this point, everything is working just fine.
However, lets now take a close look at the current flowing in the neutral wire. It'll be the sum of the three individual component flows, i.e. the sum of three sine waves, each 120 degrees out of phase with respect to the others.
If you either draw it out, or sum it up mathematically, those three sine waves always add up to zero, at any point in time. This in turn means that there's actually no current flowing in that huge return wire. So why not just remove it, and let the three hot wires carry on doing what they're doing.
In practice, this works well enough that we can transmit power over large distances without an explicit return wire. Due to imbalances in the loads, there will be some return current, but it's generally small enough that using Earth as a return is sufficient.
$endgroup$
$begingroup$
Actually, you don't even need the earth as a return. A delta-star transformer (what is found in most cases where voltage is stepped down for final use) converts line-neutral loads to line-line loads. Any imbalance in loading simply shows up as an imbalance of phase currents, not also a neutral current.
$endgroup$
– Someone Somewhere
May 6 at 0:10
$begingroup$
Star systems typically use a neutral conductor capable of carrying the same current as the phase conductors (or slightly more due to harmonics). Going smaller is not advisable as it is entirely possible for one phase to be very heavily loaded while the others are light.
$endgroup$
– Someone Somewhere
May 6 at 0:12
add a comment |
Your Answer
StackExchange.ifUsing("editor", function ()
return StackExchange.using("schematics", function ()
StackExchange.schematics.init();
);
, "cicuitlab");
StackExchange.ready(function()
var channelOptions =
tags: "".split(" "),
id: "135"
;
initTagRenderer("".split(" "), "".split(" "), channelOptions);
StackExchange.using("externalEditor", function()
// Have to fire editor after snippets, if snippets enabled
if (StackExchange.settings.snippets.snippetsEnabled)
StackExchange.using("snippets", function()
createEditor();
);
else
createEditor();
);
function createEditor()
StackExchange.prepareEditor(
heartbeatType: 'answer',
autoActivateHeartbeat: false,
convertImagesToLinks: false,
noModals: true,
showLowRepImageUploadWarning: true,
reputationToPostImages: null,
bindNavPrevention: true,
postfix: "",
imageUploader:
brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
allowUrls: true
,
onDemand: true,
discardSelector: ".discard-answer"
,immediatelyShowMarkdownHelp:true
);
);
Sign up or log in
StackExchange.ready(function ()
StackExchange.helpers.onClickDraftSave('#login-link');
);
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function ()
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2felectronics.stackexchange.com%2fquestions%2f437005%2fdoes-the-neutral-wire-have-any-voltage%23new-answer', 'question_page');
);
Post as a guest
Required, but never shown
4 Answers
4
active
oldest
votes
4 Answers
4
active
oldest
votes
active
oldest
votes
active
oldest
votes
$begingroup$
The neutral wire is defined to be 0V. And each phase individually has a voltage relative to neutral of 115V if you are in the US, and 230V if you are in most of Europe.
But because the three phases are 120 deg out of phase compared to each other this results in a voltage difference of 115V * sqrt(3) = 200V (or 230V * sqrt(3) = 400V) between any two phases.
Depending on the type of mains distribution system you've got in the country you live (I don't know how it is in the US) the neutral wire might be connected to earth at the power company. Keep in mind however, that even though the neutral wire might be connected to earth, this doesn't mean that it is actually at earth potential, because a return current might be flowing in the neutral wire, and due to the resistance in the wire this will cause a voltage at your end of the neutral wire.
It is also important to keep in mind that in many countries the mains plugs we use can actually be turned 180 deg putting line where neutral was supposed to be, meaning that with these kinds of systems you can never be sure if your neutral is actually neutral or line (BE CAREFUL!)
So to sum it up: The neutral wire is defined to be 0V. But will typically be at some voltage potential (relative to earth).
$endgroup$
1
$begingroup$
Sometimes, earth is defined to be zero volts instead of neutral. Though they're nominally the same, they can differ. This can be important, and I feel like it ought to be mentioned at least.
$endgroup$
– Hearth
May 5 at 16:21
add a comment |
$begingroup$
The neutral wire is defined to be 0V. And each phase individually has a voltage relative to neutral of 115V if you are in the US, and 230V if you are in most of Europe.
But because the three phases are 120 deg out of phase compared to each other this results in a voltage difference of 115V * sqrt(3) = 200V (or 230V * sqrt(3) = 400V) between any two phases.
Depending on the type of mains distribution system you've got in the country you live (I don't know how it is in the US) the neutral wire might be connected to earth at the power company. Keep in mind however, that even though the neutral wire might be connected to earth, this doesn't mean that it is actually at earth potential, because a return current might be flowing in the neutral wire, and due to the resistance in the wire this will cause a voltage at your end of the neutral wire.
It is also important to keep in mind that in many countries the mains plugs we use can actually be turned 180 deg putting line where neutral was supposed to be, meaning that with these kinds of systems you can never be sure if your neutral is actually neutral or line (BE CAREFUL!)
So to sum it up: The neutral wire is defined to be 0V. But will typically be at some voltage potential (relative to earth).
$endgroup$
1
$begingroup$
Sometimes, earth is defined to be zero volts instead of neutral. Though they're nominally the same, they can differ. This can be important, and I feel like it ought to be mentioned at least.
$endgroup$
– Hearth
May 5 at 16:21
add a comment |
$begingroup$
The neutral wire is defined to be 0V. And each phase individually has a voltage relative to neutral of 115V if you are in the US, and 230V if you are in most of Europe.
But because the three phases are 120 deg out of phase compared to each other this results in a voltage difference of 115V * sqrt(3) = 200V (or 230V * sqrt(3) = 400V) between any two phases.
Depending on the type of mains distribution system you've got in the country you live (I don't know how it is in the US) the neutral wire might be connected to earth at the power company. Keep in mind however, that even though the neutral wire might be connected to earth, this doesn't mean that it is actually at earth potential, because a return current might be flowing in the neutral wire, and due to the resistance in the wire this will cause a voltage at your end of the neutral wire.
It is also important to keep in mind that in many countries the mains plugs we use can actually be turned 180 deg putting line where neutral was supposed to be, meaning that with these kinds of systems you can never be sure if your neutral is actually neutral or line (BE CAREFUL!)
So to sum it up: The neutral wire is defined to be 0V. But will typically be at some voltage potential (relative to earth).
$endgroup$
The neutral wire is defined to be 0V. And each phase individually has a voltage relative to neutral of 115V if you are in the US, and 230V if you are in most of Europe.
But because the three phases are 120 deg out of phase compared to each other this results in a voltage difference of 115V * sqrt(3) = 200V (or 230V * sqrt(3) = 400V) between any two phases.
Depending on the type of mains distribution system you've got in the country you live (I don't know how it is in the US) the neutral wire might be connected to earth at the power company. Keep in mind however, that even though the neutral wire might be connected to earth, this doesn't mean that it is actually at earth potential, because a return current might be flowing in the neutral wire, and due to the resistance in the wire this will cause a voltage at your end of the neutral wire.
It is also important to keep in mind that in many countries the mains plugs we use can actually be turned 180 deg putting line where neutral was supposed to be, meaning that with these kinds of systems you can never be sure if your neutral is actually neutral or line (BE CAREFUL!)
So to sum it up: The neutral wire is defined to be 0V. But will typically be at some voltage potential (relative to earth).
answered May 5 at 13:00
VinzentVinzent
75718
75718
1
$begingroup$
Sometimes, earth is defined to be zero volts instead of neutral. Though they're nominally the same, they can differ. This can be important, and I feel like it ought to be mentioned at least.
$endgroup$
– Hearth
May 5 at 16:21
add a comment |
1
$begingroup$
Sometimes, earth is defined to be zero volts instead of neutral. Though they're nominally the same, they can differ. This can be important, and I feel like it ought to be mentioned at least.
$endgroup$
– Hearth
May 5 at 16:21
1
1
$begingroup$
Sometimes, earth is defined to be zero volts instead of neutral. Though they're nominally the same, they can differ. This can be important, and I feel like it ought to be mentioned at least.
$endgroup$
– Hearth
May 5 at 16:21
$begingroup$
Sometimes, earth is defined to be zero volts instead of neutral. Though they're nominally the same, they can differ. This can be important, and I feel like it ought to be mentioned at least.
$endgroup$
– Hearth
May 5 at 16:21
add a comment |
$begingroup$
The original article you've quoted is garbled.
... the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact).
It can't be three times higher and $ sqrt 3$ times higher simultaneously. The correct value is $ sqrt 3$ times higher.
Figure 1. The diagram in question. Source: PacketPower.
When he says the X-N voltage is 120 V, with N being the reference voltage, is the reference voltage 0 V or does it have some value?
The reference is the wye (star) point where the three windings share a common node. In this diagram it is neutralised by connecting to Earth. (That means that this conductor should not see any significant voltage on it with respect to earth.) There will be 120 V between each of the phases and the wye point whether it is earthed or not.
From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?
It depends on local regulations. If we're dealing with a transformer secondary here then typically the primary will be delta powered so there may be no neutral on the incoming supply. The solution is to ground the wye to the building's earth bonding in which case it would be the same as earth grounding. In the case of a ship, for example, the "earth" would be the ship's hull.
Figure 2. A delta-wye (delta-star) transformer connection. Source: Gamatronic.
Here we can see that there is no neutral connection on the incoming supply. Using a wye configuration on the secondary allows us to create one for internal use. The wye point can be left floating or can be grounded.
$endgroup$
$begingroup$
"Here we can see that there is no neutral connection on the incoming supply." So what provides the return path for flow of current?
$endgroup$
– noorav
May 5 at 13:53
$begingroup$
The other two phases. See my answer to How do remaining two phases act as return path in three phase system?
$endgroup$
– Transistor
May 5 at 14:21
add a comment |
$begingroup$
The original article you've quoted is garbled.
... the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact).
It can't be three times higher and $ sqrt 3$ times higher simultaneously. The correct value is $ sqrt 3$ times higher.
Figure 1. The diagram in question. Source: PacketPower.
When he says the X-N voltage is 120 V, with N being the reference voltage, is the reference voltage 0 V or does it have some value?
The reference is the wye (star) point where the three windings share a common node. In this diagram it is neutralised by connecting to Earth. (That means that this conductor should not see any significant voltage on it with respect to earth.) There will be 120 V between each of the phases and the wye point whether it is earthed or not.
From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?
It depends on local regulations. If we're dealing with a transformer secondary here then typically the primary will be delta powered so there may be no neutral on the incoming supply. The solution is to ground the wye to the building's earth bonding in which case it would be the same as earth grounding. In the case of a ship, for example, the "earth" would be the ship's hull.
Figure 2. A delta-wye (delta-star) transformer connection. Source: Gamatronic.
Here we can see that there is no neutral connection on the incoming supply. Using a wye configuration on the secondary allows us to create one for internal use. The wye point can be left floating or can be grounded.
$endgroup$
$begingroup$
"Here we can see that there is no neutral connection on the incoming supply." So what provides the return path for flow of current?
$endgroup$
– noorav
May 5 at 13:53
$begingroup$
The other two phases. See my answer to How do remaining two phases act as return path in three phase system?
$endgroup$
– Transistor
May 5 at 14:21
add a comment |
$begingroup$
The original article you've quoted is garbled.
... the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact).
It can't be three times higher and $ sqrt 3$ times higher simultaneously. The correct value is $ sqrt 3$ times higher.
Figure 1. The diagram in question. Source: PacketPower.
When he says the X-N voltage is 120 V, with N being the reference voltage, is the reference voltage 0 V or does it have some value?
The reference is the wye (star) point where the three windings share a common node. In this diagram it is neutralised by connecting to Earth. (That means that this conductor should not see any significant voltage on it with respect to earth.) There will be 120 V between each of the phases and the wye point whether it is earthed or not.
From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?
It depends on local regulations. If we're dealing with a transformer secondary here then typically the primary will be delta powered so there may be no neutral on the incoming supply. The solution is to ground the wye to the building's earth bonding in which case it would be the same as earth grounding. In the case of a ship, for example, the "earth" would be the ship's hull.
Figure 2. A delta-wye (delta-star) transformer connection. Source: Gamatronic.
Here we can see that there is no neutral connection on the incoming supply. Using a wye configuration on the secondary allows us to create one for internal use. The wye point can be left floating or can be grounded.
$endgroup$
The original article you've quoted is garbled.
... the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact).
It can't be three times higher and $ sqrt 3$ times higher simultaneously. The correct value is $ sqrt 3$ times higher.
Figure 1. The diagram in question. Source: PacketPower.
When he says the X-N voltage is 120 V, with N being the reference voltage, is the reference voltage 0 V or does it have some value?
The reference is the wye (star) point where the three windings share a common node. In this diagram it is neutralised by connecting to Earth. (That means that this conductor should not see any significant voltage on it with respect to earth.) There will be 120 V between each of the phases and the wye point whether it is earthed or not.
From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?
It depends on local regulations. If we're dealing with a transformer secondary here then typically the primary will be delta powered so there may be no neutral on the incoming supply. The solution is to ground the wye to the building's earth bonding in which case it would be the same as earth grounding. In the case of a ship, for example, the "earth" would be the ship's hull.
Figure 2. A delta-wye (delta-star) transformer connection. Source: Gamatronic.
Here we can see that there is no neutral connection on the incoming supply. Using a wye configuration on the secondary allows us to create one for internal use. The wye point can be left floating or can be grounded.
answered May 5 at 13:02
TransistorTransistor
91.4k788195
91.4k788195
$begingroup$
"Here we can see that there is no neutral connection on the incoming supply." So what provides the return path for flow of current?
$endgroup$
– noorav
May 5 at 13:53
$begingroup$
The other two phases. See my answer to How do remaining two phases act as return path in three phase system?
$endgroup$
– Transistor
May 5 at 14:21
add a comment |
$begingroup$
"Here we can see that there is no neutral connection on the incoming supply." So what provides the return path for flow of current?
$endgroup$
– noorav
May 5 at 13:53
$begingroup$
The other two phases. See my answer to How do remaining two phases act as return path in three phase system?
$endgroup$
– Transistor
May 5 at 14:21
$begingroup$
"Here we can see that there is no neutral connection on the incoming supply." So what provides the return path for flow of current?
$endgroup$
– noorav
May 5 at 13:53
$begingroup$
"Here we can see that there is no neutral connection on the incoming supply." So what provides the return path for flow of current?
$endgroup$
– noorav
May 5 at 13:53
$begingroup$
The other two phases. See my answer to How do remaining two phases act as return path in three phase system?
$endgroup$
– Transistor
May 5 at 14:21
$begingroup$
The other two phases. See my answer to How do remaining two phases act as return path in three phase system?
$endgroup$
– Transistor
May 5 at 14:21
add a comment |
$begingroup$
The neutral wire is grounded, so if you literally took a multi-meter and tried to read voltage between the neutral wire and ground, you will read 0 voltage. Please note, this is for a healthy working balanced system.
So yes, consider the neutral wire 0V if everything is in working order.
$endgroup$
$begingroup$
That depends completely on the type of distribution system is used in the country you live in. In most of Europe the neutral is indeed connected to earth at the power company, but this is not always the case/ not the case in all countries..
$endgroup$
– Vinzent
May 5 at 13:02
$begingroup$
Do you have an example where someone is running power through the neutral wire? Would be interesting to see this setup.
$endgroup$
– Busta
May 5 at 13:05
1
$begingroup$
You can read this wiki page about earthing systems: en.wikipedia.org/wiki/Earthing_system, It describes the different types of earthing systems, such as TN, TT, IN and IT..
$endgroup$
– Vinzent
May 5 at 13:10
$begingroup$
Thanks for the link. So I will default that my answer works in traditional WYE (Star) / Delta systems that use a 4-wire 3-phase traditional set-up where the neutral is tied to the ground. Hence, if you tried to read voltage between neutral and ground...theoretically you should get 0volts but your answer explained why you may see some voltage.. The original question gave the assumption that the neutral wire is grounded.
$endgroup$
– Busta
May 5 at 13:18
add a comment |
$begingroup$
The neutral wire is grounded, so if you literally took a multi-meter and tried to read voltage between the neutral wire and ground, you will read 0 voltage. Please note, this is for a healthy working balanced system.
So yes, consider the neutral wire 0V if everything is in working order.
$endgroup$
$begingroup$
That depends completely on the type of distribution system is used in the country you live in. In most of Europe the neutral is indeed connected to earth at the power company, but this is not always the case/ not the case in all countries..
$endgroup$
– Vinzent
May 5 at 13:02
$begingroup$
Do you have an example where someone is running power through the neutral wire? Would be interesting to see this setup.
$endgroup$
– Busta
May 5 at 13:05
1
$begingroup$
You can read this wiki page about earthing systems: en.wikipedia.org/wiki/Earthing_system, It describes the different types of earthing systems, such as TN, TT, IN and IT..
$endgroup$
– Vinzent
May 5 at 13:10
$begingroup$
Thanks for the link. So I will default that my answer works in traditional WYE (Star) / Delta systems that use a 4-wire 3-phase traditional set-up where the neutral is tied to the ground. Hence, if you tried to read voltage between neutral and ground...theoretically you should get 0volts but your answer explained why you may see some voltage.. The original question gave the assumption that the neutral wire is grounded.
$endgroup$
– Busta
May 5 at 13:18
add a comment |
$begingroup$
The neutral wire is grounded, so if you literally took a multi-meter and tried to read voltage between the neutral wire and ground, you will read 0 voltage. Please note, this is for a healthy working balanced system.
So yes, consider the neutral wire 0V if everything is in working order.
$endgroup$
The neutral wire is grounded, so if you literally took a multi-meter and tried to read voltage between the neutral wire and ground, you will read 0 voltage. Please note, this is for a healthy working balanced system.
So yes, consider the neutral wire 0V if everything is in working order.
answered May 5 at 13:00
BustaBusta
206
206
$begingroup$
That depends completely on the type of distribution system is used in the country you live in. In most of Europe the neutral is indeed connected to earth at the power company, but this is not always the case/ not the case in all countries..
$endgroup$
– Vinzent
May 5 at 13:02
$begingroup$
Do you have an example where someone is running power through the neutral wire? Would be interesting to see this setup.
$endgroup$
– Busta
May 5 at 13:05
1
$begingroup$
You can read this wiki page about earthing systems: en.wikipedia.org/wiki/Earthing_system, It describes the different types of earthing systems, such as TN, TT, IN and IT..
$endgroup$
– Vinzent
May 5 at 13:10
$begingroup$
Thanks for the link. So I will default that my answer works in traditional WYE (Star) / Delta systems that use a 4-wire 3-phase traditional set-up where the neutral is tied to the ground. Hence, if you tried to read voltage between neutral and ground...theoretically you should get 0volts but your answer explained why you may see some voltage.. The original question gave the assumption that the neutral wire is grounded.
$endgroup$
– Busta
May 5 at 13:18
add a comment |
$begingroup$
That depends completely on the type of distribution system is used in the country you live in. In most of Europe the neutral is indeed connected to earth at the power company, but this is not always the case/ not the case in all countries..
$endgroup$
– Vinzent
May 5 at 13:02
$begingroup$
Do you have an example where someone is running power through the neutral wire? Would be interesting to see this setup.
$endgroup$
– Busta
May 5 at 13:05
1
$begingroup$
You can read this wiki page about earthing systems: en.wikipedia.org/wiki/Earthing_system, It describes the different types of earthing systems, such as TN, TT, IN and IT..
$endgroup$
– Vinzent
May 5 at 13:10
$begingroup$
Thanks for the link. So I will default that my answer works in traditional WYE (Star) / Delta systems that use a 4-wire 3-phase traditional set-up where the neutral is tied to the ground. Hence, if you tried to read voltage between neutral and ground...theoretically you should get 0volts but your answer explained why you may see some voltage.. The original question gave the assumption that the neutral wire is grounded.
$endgroup$
– Busta
May 5 at 13:18
$begingroup$
That depends completely on the type of distribution system is used in the country you live in. In most of Europe the neutral is indeed connected to earth at the power company, but this is not always the case/ not the case in all countries..
$endgroup$
– Vinzent
May 5 at 13:02
$begingroup$
That depends completely on the type of distribution system is used in the country you live in. In most of Europe the neutral is indeed connected to earth at the power company, but this is not always the case/ not the case in all countries..
$endgroup$
– Vinzent
May 5 at 13:02
$begingroup$
Do you have an example where someone is running power through the neutral wire? Would be interesting to see this setup.
$endgroup$
– Busta
May 5 at 13:05
$begingroup$
Do you have an example where someone is running power through the neutral wire? Would be interesting to see this setup.
$endgroup$
– Busta
May 5 at 13:05
1
1
$begingroup$
You can read this wiki page about earthing systems: en.wikipedia.org/wiki/Earthing_system, It describes the different types of earthing systems, such as TN, TT, IN and IT..
$endgroup$
– Vinzent
May 5 at 13:10
$begingroup$
You can read this wiki page about earthing systems: en.wikipedia.org/wiki/Earthing_system, It describes the different types of earthing systems, such as TN, TT, IN and IT..
$endgroup$
– Vinzent
May 5 at 13:10
$begingroup$
Thanks for the link. So I will default that my answer works in traditional WYE (Star) / Delta systems that use a 4-wire 3-phase traditional set-up where the neutral is tied to the ground. Hence, if you tried to read voltage between neutral and ground...theoretically you should get 0volts but your answer explained why you may see some voltage.. The original question gave the assumption that the neutral wire is grounded.
$endgroup$
– Busta
May 5 at 13:18
$begingroup$
Thanks for the link. So I will default that my answer works in traditional WYE (Star) / Delta systems that use a 4-wire 3-phase traditional set-up where the neutral is tied to the ground. Hence, if you tried to read voltage between neutral and ground...theoretically you should get 0volts but your answer explained why you may see some voltage.. The original question gave the assumption that the neutral wire is grounded.
$endgroup$
– Busta
May 5 at 13:18
add a comment |
$begingroup$
"Here we can see that there is no neutral connection on the incoming supply."
So what provides the return path for flow of current?
This was asked as a comment, but to answer it I need far more space than a comment allows.
With a simple two wire AC connection, the outgoing current on the hot wire is has the exact same absolute magnitude as the return current in the neutral wire, but they have opposite signs. In addition to this, the current is actually a sine wave.
Now, lets take three copies of this, but adjust the phase of two of the circuits so that all three are 120 degrees out of phase with respect to each other.
Next, lets replace the three neutral wires with one big wire three times the capacity. Up to this point, everything is working just fine.
However, lets now take a close look at the current flowing in the neutral wire. It'll be the sum of the three individual component flows, i.e. the sum of three sine waves, each 120 degrees out of phase with respect to the others.
If you either draw it out, or sum it up mathematically, those three sine waves always add up to zero, at any point in time. This in turn means that there's actually no current flowing in that huge return wire. So why not just remove it, and let the three hot wires carry on doing what they're doing.
In practice, this works well enough that we can transmit power over large distances without an explicit return wire. Due to imbalances in the loads, there will be some return current, but it's generally small enough that using Earth as a return is sufficient.
$endgroup$
$begingroup$
Actually, you don't even need the earth as a return. A delta-star transformer (what is found in most cases where voltage is stepped down for final use) converts line-neutral loads to line-line loads. Any imbalance in loading simply shows up as an imbalance of phase currents, not also a neutral current.
$endgroup$
– Someone Somewhere
May 6 at 0:10
$begingroup$
Star systems typically use a neutral conductor capable of carrying the same current as the phase conductors (or slightly more due to harmonics). Going smaller is not advisable as it is entirely possible for one phase to be very heavily loaded while the others are light.
$endgroup$
– Someone Somewhere
May 6 at 0:12
add a comment |
$begingroup$
"Here we can see that there is no neutral connection on the incoming supply."
So what provides the return path for flow of current?
This was asked as a comment, but to answer it I need far more space than a comment allows.
With a simple two wire AC connection, the outgoing current on the hot wire is has the exact same absolute magnitude as the return current in the neutral wire, but they have opposite signs. In addition to this, the current is actually a sine wave.
Now, lets take three copies of this, but adjust the phase of two of the circuits so that all three are 120 degrees out of phase with respect to each other.
Next, lets replace the three neutral wires with one big wire three times the capacity. Up to this point, everything is working just fine.
However, lets now take a close look at the current flowing in the neutral wire. It'll be the sum of the three individual component flows, i.e. the sum of three sine waves, each 120 degrees out of phase with respect to the others.
If you either draw it out, or sum it up mathematically, those three sine waves always add up to zero, at any point in time. This in turn means that there's actually no current flowing in that huge return wire. So why not just remove it, and let the three hot wires carry on doing what they're doing.
In practice, this works well enough that we can transmit power over large distances without an explicit return wire. Due to imbalances in the loads, there will be some return current, but it's generally small enough that using Earth as a return is sufficient.
$endgroup$
$begingroup$
Actually, you don't even need the earth as a return. A delta-star transformer (what is found in most cases where voltage is stepped down for final use) converts line-neutral loads to line-line loads. Any imbalance in loading simply shows up as an imbalance of phase currents, not also a neutral current.
$endgroup$
– Someone Somewhere
May 6 at 0:10
$begingroup$
Star systems typically use a neutral conductor capable of carrying the same current as the phase conductors (or slightly more due to harmonics). Going smaller is not advisable as it is entirely possible for one phase to be very heavily loaded while the others are light.
$endgroup$
– Someone Somewhere
May 6 at 0:12
add a comment |
$begingroup$
"Here we can see that there is no neutral connection on the incoming supply."
So what provides the return path for flow of current?
This was asked as a comment, but to answer it I need far more space than a comment allows.
With a simple two wire AC connection, the outgoing current on the hot wire is has the exact same absolute magnitude as the return current in the neutral wire, but they have opposite signs. In addition to this, the current is actually a sine wave.
Now, lets take three copies of this, but adjust the phase of two of the circuits so that all three are 120 degrees out of phase with respect to each other.
Next, lets replace the three neutral wires with one big wire three times the capacity. Up to this point, everything is working just fine.
However, lets now take a close look at the current flowing in the neutral wire. It'll be the sum of the three individual component flows, i.e. the sum of three sine waves, each 120 degrees out of phase with respect to the others.
If you either draw it out, or sum it up mathematically, those three sine waves always add up to zero, at any point in time. This in turn means that there's actually no current flowing in that huge return wire. So why not just remove it, and let the three hot wires carry on doing what they're doing.
In practice, this works well enough that we can transmit power over large distances without an explicit return wire. Due to imbalances in the loads, there will be some return current, but it's generally small enough that using Earth as a return is sufficient.
$endgroup$
"Here we can see that there is no neutral connection on the incoming supply."
So what provides the return path for flow of current?
This was asked as a comment, but to answer it I need far more space than a comment allows.
With a simple two wire AC connection, the outgoing current on the hot wire is has the exact same absolute magnitude as the return current in the neutral wire, but they have opposite signs. In addition to this, the current is actually a sine wave.
Now, lets take three copies of this, but adjust the phase of two of the circuits so that all three are 120 degrees out of phase with respect to each other.
Next, lets replace the three neutral wires with one big wire three times the capacity. Up to this point, everything is working just fine.
However, lets now take a close look at the current flowing in the neutral wire. It'll be the sum of the three individual component flows, i.e. the sum of three sine waves, each 120 degrees out of phase with respect to the others.
If you either draw it out, or sum it up mathematically, those three sine waves always add up to zero, at any point in time. This in turn means that there's actually no current flowing in that huge return wire. So why not just remove it, and let the three hot wires carry on doing what they're doing.
In practice, this works well enough that we can transmit power over large distances without an explicit return wire. Due to imbalances in the loads, there will be some return current, but it's generally small enough that using Earth as a return is sufficient.
edited May 5 at 21:33
answered May 5 at 21:21
dgnuffdgnuff
1084
1084
$begingroup$
Actually, you don't even need the earth as a return. A delta-star transformer (what is found in most cases where voltage is stepped down for final use) converts line-neutral loads to line-line loads. Any imbalance in loading simply shows up as an imbalance of phase currents, not also a neutral current.
$endgroup$
– Someone Somewhere
May 6 at 0:10
$begingroup$
Star systems typically use a neutral conductor capable of carrying the same current as the phase conductors (or slightly more due to harmonics). Going smaller is not advisable as it is entirely possible for one phase to be very heavily loaded while the others are light.
$endgroup$
– Someone Somewhere
May 6 at 0:12
add a comment |
$begingroup$
Actually, you don't even need the earth as a return. A delta-star transformer (what is found in most cases where voltage is stepped down for final use) converts line-neutral loads to line-line loads. Any imbalance in loading simply shows up as an imbalance of phase currents, not also a neutral current.
$endgroup$
– Someone Somewhere
May 6 at 0:10
$begingroup$
Star systems typically use a neutral conductor capable of carrying the same current as the phase conductors (or slightly more due to harmonics). Going smaller is not advisable as it is entirely possible for one phase to be very heavily loaded while the others are light.
$endgroup$
– Someone Somewhere
May 6 at 0:12
$begingroup$
Actually, you don't even need the earth as a return. A delta-star transformer (what is found in most cases where voltage is stepped down for final use) converts line-neutral loads to line-line loads. Any imbalance in loading simply shows up as an imbalance of phase currents, not also a neutral current.
$endgroup$
– Someone Somewhere
May 6 at 0:10
$begingroup$
Actually, you don't even need the earth as a return. A delta-star transformer (what is found in most cases where voltage is stepped down for final use) converts line-neutral loads to line-line loads. Any imbalance in loading simply shows up as an imbalance of phase currents, not also a neutral current.
$endgroup$
– Someone Somewhere
May 6 at 0:10
$begingroup$
Star systems typically use a neutral conductor capable of carrying the same current as the phase conductors (or slightly more due to harmonics). Going smaller is not advisable as it is entirely possible for one phase to be very heavily loaded while the others are light.
$endgroup$
– Someone Somewhere
May 6 at 0:12
$begingroup$
Star systems typically use a neutral conductor capable of carrying the same current as the phase conductors (or slightly more due to harmonics). Going smaller is not advisable as it is entirely possible for one phase to be very heavily loaded while the others are light.
$endgroup$
– Someone Somewhere
May 6 at 0:12
add a comment |
Thanks for contributing an answer to Electrical Engineering Stack Exchange!
- Please be sure to answer the question. Provide details and share your research!
But avoid …
- Asking for help, clarification, or responding to other answers.
- Making statements based on opinion; back them up with references or personal experience.
Use MathJax to format equations. MathJax reference.
To learn more, see our tips on writing great answers.
Sign up or log in
StackExchange.ready(function ()
StackExchange.helpers.onClickDraftSave('#login-link');
);
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function ()
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2felectronics.stackexchange.com%2fquestions%2f437005%2fdoes-the-neutral-wire-have-any-voltage%23new-answer', 'question_page');
);
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function ()
StackExchange.helpers.onClickDraftSave('#login-link');
);
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function ()
StackExchange.helpers.onClickDraftSave('#login-link');
);
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function ()
StackExchange.helpers.onClickDraftSave('#login-link');
);
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
4
$begingroup$
I think you're not understanding something here. There is no absolute value of voltage, just voltage differences.
$endgroup$
– Hearth
May 5 at 12:43
$begingroup$
No I did understand that part. I'm saying the 120V voltage difference between X-N can be either 121-1 or 120-0. Which one is it?
$endgroup$
– noorav
May 5 at 12:45
6
$begingroup$
The fact that you're asking that shows that you don't understand.
$endgroup$
– Hearth
May 5 at 12:46
$begingroup$
I'm sorry, but where is my understanding flawed? This is how I've been learning about voltage difference for so long. Could you please correct me
$endgroup$
– noorav
May 5 at 12:47
3
$begingroup$
Well, you're asking whether there's a voltage on the neutral wire. A voltage relative to what?
$endgroup$
– Hearth
May 5 at 12:49