Does the neutral wire have any voltage?How do remaining two phases act as return path in three phase systemHow to find Voltage based on reference nodes?Why is using a single phase device across phases of a 3 phase outlet OK?Three phase heaters and ampsHow to calculate the neutral wire size of a home (department)?What are the adavantages of neutral vs. isolated grounding?Grounding conductor has a non-zero voltage (i.e. with respect to “true” ground). Why?Why isn't line to line voltage zero?3 phase generator residual voltageHow does circuit completes when physical ground(earth) is used as neutral?How are the individual homes connected in a 3 phase power distribution system (power grid) so that they have correct voltage?Why is earth at 0 V with respect to phase?

Why is the marginal distribution/marginal probability described as "marginal"?

Does a non-singular matrix have a large minor with disjoint rows and columns and full rank?

Holding rent money for my friend which amounts to over $10k?

Why does string strummed with finger sound different from the one strummed with pick?

He is the first man to arrive here

How can I safely determine the output voltage and current of a transformer?

Non-African Click Languages

Why did the soldiers of the North disobey Jon?

Do high-wing aircraft represent more difficult engineering challenges than low-wing aircraft?

I recently started my machine learning PhD and I have absolutely no idea what I'm doing

Is it standard for US-based universities to consider the ethnicity of an applicant during PhD admissions?

Canadian citizen who is presently in litigation with a US-based company

How to generate a triangular grid from a list of points

Would it be fair to use 1d30 (instead of rolling 2d20 and taking the higher die) for advantage rolls?

Why are lawsuits between the President and Congress not automatically sent to the Supreme Court

How can we delete item permanently without storing in Recycle Bin?

Promotion comes with unexpected 24/7/365 on-call

Is there an academic word that means "to split hairs over"?

AD: OU for system administrator accounts

What technology would Dwarves need to forge titanium?

Why aren't satellites disintegrated even though they orbit earth within their Roche Limits?

Why is Drogon so much better in battle than Rhaegal and Viserion?

multiline equation inside a matrix that is a part of multiline equation

Is Precocious Apprentice enough for Mystic Theurge?



Does the neutral wire have any voltage?


How do remaining two phases act as return path in three phase systemHow to find Voltage based on reference nodes?Why is using a single phase device across phases of a 3 phase outlet OK?Three phase heaters and ampsHow to calculate the neutral wire size of a home (department)?What are the adavantages of neutral vs. isolated grounding?Grounding conductor has a non-zero voltage (i.e. with respect to “true” ground). Why?Why isn't line to line voltage zero?3 phase generator residual voltageHow does circuit completes when physical ground(earth) is used as neutral?How are the individual homes connected in a 3 phase power distribution system (power grid) so that they have correct voltage?Why is earth at 0 V with respect to phase?






.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty,.everyoneloves__bot-mid-leaderboard:empty margin-bottom:0;








5












$begingroup$


In this article, the author talks about 3 phase and the magic of a missing neutral wire. And there's the following paragraph:




In a 3-phase system the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact). If your X-N (and Y-N and Z-N) voltage is 120V (common in the US), the X-Y (and Y-Z and Z-X) voltages (a.k.a. “cross-phase” voltages) will be 120V * 1.73 = 208V.




When he says the X-N voltage is 120V, with N being the reference voltage, is the reference voltage 0V or does it have some value?



From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?










share|improve this question











$endgroup$







  • 4




    $begingroup$
    I think you're not understanding something here. There is no absolute value of voltage, just voltage differences.
    $endgroup$
    – Hearth
    May 5 at 12:43










  • $begingroup$
    No I did understand that part. I'm saying the 120V voltage difference between X-N can be either 121-1 or 120-0. Which one is it?
    $endgroup$
    – noorav
    May 5 at 12:45






  • 6




    $begingroup$
    The fact that you're asking that shows that you don't understand.
    $endgroup$
    – Hearth
    May 5 at 12:46










  • $begingroup$
    I'm sorry, but where is my understanding flawed? This is how I've been learning about voltage difference for so long. Could you please correct me
    $endgroup$
    – noorav
    May 5 at 12:47






  • 3




    $begingroup$
    Well, you're asking whether there's a voltage on the neutral wire. A voltage relative to what?
    $endgroup$
    – Hearth
    May 5 at 12:49

















5












$begingroup$


In this article, the author talks about 3 phase and the magic of a missing neutral wire. And there's the following paragraph:




In a 3-phase system the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact). If your X-N (and Y-N and Z-N) voltage is 120V (common in the US), the X-Y (and Y-Z and Z-X) voltages (a.k.a. “cross-phase” voltages) will be 120V * 1.73 = 208V.




When he says the X-N voltage is 120V, with N being the reference voltage, is the reference voltage 0V or does it have some value?



From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?










share|improve this question











$endgroup$







  • 4




    $begingroup$
    I think you're not understanding something here. There is no absolute value of voltage, just voltage differences.
    $endgroup$
    – Hearth
    May 5 at 12:43










  • $begingroup$
    No I did understand that part. I'm saying the 120V voltage difference between X-N can be either 121-1 or 120-0. Which one is it?
    $endgroup$
    – noorav
    May 5 at 12:45






  • 6




    $begingroup$
    The fact that you're asking that shows that you don't understand.
    $endgroup$
    – Hearth
    May 5 at 12:46










  • $begingroup$
    I'm sorry, but where is my understanding flawed? This is how I've been learning about voltage difference for so long. Could you please correct me
    $endgroup$
    – noorav
    May 5 at 12:47






  • 3




    $begingroup$
    Well, you're asking whether there's a voltage on the neutral wire. A voltage relative to what?
    $endgroup$
    – Hearth
    May 5 at 12:49













5












5








5


3



$begingroup$


In this article, the author talks about 3 phase and the magic of a missing neutral wire. And there's the following paragraph:




In a 3-phase system the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact). If your X-N (and Y-N and Z-N) voltage is 120V (common in the US), the X-Y (and Y-Z and Z-X) voltages (a.k.a. “cross-phase” voltages) will be 120V * 1.73 = 208V.




When he says the X-N voltage is 120V, with N being the reference voltage, is the reference voltage 0V or does it have some value?



From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?










share|improve this question











$endgroup$




In this article, the author talks about 3 phase and the magic of a missing neutral wire. And there's the following paragraph:




In a 3-phase system the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact). If your X-N (and Y-N and Z-N) voltage is 120V (common in the US), the X-Y (and Y-Z and Z-X) voltages (a.k.a. “cross-phase” voltages) will be 120V * 1.73 = 208V.




When he says the X-N voltage is 120V, with N being the reference voltage, is the reference voltage 0V or does it have some value?



From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?







power-supply power wire three-phase neutral






share|improve this question















share|improve this question













share|improve this question




share|improve this question








edited May 5 at 12:45









JRE

25.4k64585




25.4k64585










asked May 5 at 12:41









nooravnoorav

807




807







  • 4




    $begingroup$
    I think you're not understanding something here. There is no absolute value of voltage, just voltage differences.
    $endgroup$
    – Hearth
    May 5 at 12:43










  • $begingroup$
    No I did understand that part. I'm saying the 120V voltage difference between X-N can be either 121-1 or 120-0. Which one is it?
    $endgroup$
    – noorav
    May 5 at 12:45






  • 6




    $begingroup$
    The fact that you're asking that shows that you don't understand.
    $endgroup$
    – Hearth
    May 5 at 12:46










  • $begingroup$
    I'm sorry, but where is my understanding flawed? This is how I've been learning about voltage difference for so long. Could you please correct me
    $endgroup$
    – noorav
    May 5 at 12:47






  • 3




    $begingroup$
    Well, you're asking whether there's a voltage on the neutral wire. A voltage relative to what?
    $endgroup$
    – Hearth
    May 5 at 12:49












  • 4




    $begingroup$
    I think you're not understanding something here. There is no absolute value of voltage, just voltage differences.
    $endgroup$
    – Hearth
    May 5 at 12:43










  • $begingroup$
    No I did understand that part. I'm saying the 120V voltage difference between X-N can be either 121-1 or 120-0. Which one is it?
    $endgroup$
    – noorav
    May 5 at 12:45






  • 6




    $begingroup$
    The fact that you're asking that shows that you don't understand.
    $endgroup$
    – Hearth
    May 5 at 12:46










  • $begingroup$
    I'm sorry, but where is my understanding flawed? This is how I've been learning about voltage difference for so long. Could you please correct me
    $endgroup$
    – noorav
    May 5 at 12:47






  • 3




    $begingroup$
    Well, you're asking whether there's a voltage on the neutral wire. A voltage relative to what?
    $endgroup$
    – Hearth
    May 5 at 12:49







4




4




$begingroup$
I think you're not understanding something here. There is no absolute value of voltage, just voltage differences.
$endgroup$
– Hearth
May 5 at 12:43




$begingroup$
I think you're not understanding something here. There is no absolute value of voltage, just voltage differences.
$endgroup$
– Hearth
May 5 at 12:43












$begingroup$
No I did understand that part. I'm saying the 120V voltage difference between X-N can be either 121-1 or 120-0. Which one is it?
$endgroup$
– noorav
May 5 at 12:45




$begingroup$
No I did understand that part. I'm saying the 120V voltage difference between X-N can be either 121-1 or 120-0. Which one is it?
$endgroup$
– noorav
May 5 at 12:45




6




6




$begingroup$
The fact that you're asking that shows that you don't understand.
$endgroup$
– Hearth
May 5 at 12:46




$begingroup$
The fact that you're asking that shows that you don't understand.
$endgroup$
– Hearth
May 5 at 12:46












$begingroup$
I'm sorry, but where is my understanding flawed? This is how I've been learning about voltage difference for so long. Could you please correct me
$endgroup$
– noorav
May 5 at 12:47




$begingroup$
I'm sorry, but where is my understanding flawed? This is how I've been learning about voltage difference for so long. Could you please correct me
$endgroup$
– noorav
May 5 at 12:47




3




3




$begingroup$
Well, you're asking whether there's a voltage on the neutral wire. A voltage relative to what?
$endgroup$
– Hearth
May 5 at 12:49




$begingroup$
Well, you're asking whether there's a voltage on the neutral wire. A voltage relative to what?
$endgroup$
– Hearth
May 5 at 12:49










4 Answers
4






active

oldest

votes


















8












$begingroup$

The neutral wire is defined to be 0V. And each phase individually has a voltage relative to neutral of 115V if you are in the US, and 230V if you are in most of Europe.



But because the three phases are 120 deg out of phase compared to each other this results in a voltage difference of 115V * sqrt(3) = 200V (or 230V * sqrt(3) = 400V) between any two phases.



Depending on the type of mains distribution system you've got in the country you live (I don't know how it is in the US) the neutral wire might be connected to earth at the power company. Keep in mind however, that even though the neutral wire might be connected to earth, this doesn't mean that it is actually at earth potential, because a return current might be flowing in the neutral wire, and due to the resistance in the wire this will cause a voltage at your end of the neutral wire.



It is also important to keep in mind that in many countries the mains plugs we use can actually be turned 180 deg putting line where neutral was supposed to be, meaning that with these kinds of systems you can never be sure if your neutral is actually neutral or line (BE CAREFUL!)



So to sum it up: The neutral wire is defined to be 0V. But will typically be at some voltage potential (relative to earth).






share|improve this answer









$endgroup$








  • 1




    $begingroup$
    Sometimes, earth is defined to be zero volts instead of neutral. Though they're nominally the same, they can differ. This can be important, and I feel like it ought to be mentioned at least.
    $endgroup$
    – Hearth
    May 5 at 16:21



















9












$begingroup$

The original article you've quoted is garbled.




... the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact).




It can't be three times higher and $ sqrt 3$ times higher simultaneously. The correct value is $ sqrt 3$ times higher.



enter image description here



Figure 1. The diagram in question. Source: PacketPower.




When he says the X-N voltage is 120 V, with N being the reference voltage, is the reference voltage 0 V or does it have some value?




The reference is the wye (star) point where the three windings share a common node. In this diagram it is neutralised by connecting to Earth. (That means that this conductor should not see any significant voltage on it with respect to earth.) There will be 120 V between each of the phases and the wye point whether it is earthed or not.




From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?




It depends on local regulations. If we're dealing with a transformer secondary here then typically the primary will be delta powered so there may be no neutral on the incoming supply. The solution is to ground the wye to the building's earth bonding in which case it would be the same as earth grounding. In the case of a ship, for example, the "earth" would be the ship's hull.



enter image description here



Figure 2. A delta-wye (delta-star) transformer connection. Source: Gamatronic.



Here we can see that there is no neutral connection on the incoming supply. Using a wye configuration on the secondary allows us to create one for internal use. The wye point can be left floating or can be grounded.






share|improve this answer









$endgroup$












  • $begingroup$
    "Here we can see that there is no neutral connection on the incoming supply." So what provides the return path for flow of current?
    $endgroup$
    – noorav
    May 5 at 13:53











  • $begingroup$
    The other two phases. See my answer to How do remaining two phases act as return path in three phase system?
    $endgroup$
    – Transistor
    May 5 at 14:21


















1












$begingroup$

The neutral wire is grounded, so if you literally took a multi-meter and tried to read voltage between the neutral wire and ground, you will read 0 voltage. Please note, this is for a healthy working balanced system.



So yes, consider the neutral wire 0V if everything is in working order.






share|improve this answer









$endgroup$












  • $begingroup$
    That depends completely on the type of distribution system is used in the country you live in. In most of Europe the neutral is indeed connected to earth at the power company, but this is not always the case/ not the case in all countries..
    $endgroup$
    – Vinzent
    May 5 at 13:02










  • $begingroup$
    Do you have an example where someone is running power through the neutral wire? Would be interesting to see this setup.
    $endgroup$
    – Busta
    May 5 at 13:05






  • 1




    $begingroup$
    You can read this wiki page about earthing systems: en.wikipedia.org/wiki/Earthing_system, It describes the different types of earthing systems, such as TN, TT, IN and IT..
    $endgroup$
    – Vinzent
    May 5 at 13:10










  • $begingroup$
    Thanks for the link. So I will default that my answer works in traditional WYE (Star) / Delta systems that use a 4-wire 3-phase traditional set-up where the neutral is tied to the ground. Hence, if you tried to read voltage between neutral and ground...theoretically you should get 0volts but your answer explained why you may see some voltage.. The original question gave the assumption that the neutral wire is grounded.
    $endgroup$
    – Busta
    May 5 at 13:18



















0












$begingroup$


"Here we can see that there is no neutral connection on the incoming supply."



So what provides the return path for flow of current?




This was asked as a comment, but to answer it I need far more space than a comment allows.



With a simple two wire AC connection, the outgoing current on the hot wire is has the exact same absolute magnitude as the return current in the neutral wire, but they have opposite signs. In addition to this, the current is actually a sine wave.



Now, lets take three copies of this, but adjust the phase of two of the circuits so that all three are 120 degrees out of phase with respect to each other.



Next, lets replace the three neutral wires with one big wire three times the capacity. Up to this point, everything is working just fine.



However, lets now take a close look at the current flowing in the neutral wire. It'll be the sum of the three individual component flows, i.e. the sum of three sine waves, each 120 degrees out of phase with respect to the others.



If you either draw it out, or sum it up mathematically, those three sine waves always add up to zero, at any point in time. This in turn means that there's actually no current flowing in that huge return wire. So why not just remove it, and let the three hot wires carry on doing what they're doing.



In practice, this works well enough that we can transmit power over large distances without an explicit return wire. Due to imbalances in the loads, there will be some return current, but it's generally small enough that using Earth as a return is sufficient.






share|improve this answer











$endgroup$












  • $begingroup$
    Actually, you don't even need the earth as a return. A delta-star transformer (what is found in most cases where voltage is stepped down for final use) converts line-neutral loads to line-line loads. Any imbalance in loading simply shows up as an imbalance of phase currents, not also a neutral current.
    $endgroup$
    – Someone Somewhere
    May 6 at 0:10










  • $begingroup$
    Star systems typically use a neutral conductor capable of carrying the same current as the phase conductors (or slightly more due to harmonics). Going smaller is not advisable as it is entirely possible for one phase to be very heavily loaded while the others are light.
    $endgroup$
    – Someone Somewhere
    May 6 at 0:12











Your Answer






StackExchange.ifUsing("editor", function ()
return StackExchange.using("schematics", function ()
StackExchange.schematics.init();
);
, "cicuitlab");

StackExchange.ready(function()
var channelOptions =
tags: "".split(" "),
id: "135"
;
initTagRenderer("".split(" "), "".split(" "), channelOptions);

StackExchange.using("externalEditor", function()
// Have to fire editor after snippets, if snippets enabled
if (StackExchange.settings.snippets.snippetsEnabled)
StackExchange.using("snippets", function()
createEditor();
);

else
createEditor();

);

function createEditor()
StackExchange.prepareEditor(
heartbeatType: 'answer',
autoActivateHeartbeat: false,
convertImagesToLinks: false,
noModals: true,
showLowRepImageUploadWarning: true,
reputationToPostImages: null,
bindNavPrevention: true,
postfix: "",
imageUploader:
brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
allowUrls: true
,
onDemand: true,
discardSelector: ".discard-answer"
,immediatelyShowMarkdownHelp:true
);



);













draft saved

draft discarded


















StackExchange.ready(
function ()
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2felectronics.stackexchange.com%2fquestions%2f437005%2fdoes-the-neutral-wire-have-any-voltage%23new-answer', 'question_page');

);

Post as a guest















Required, but never shown

























4 Answers
4






active

oldest

votes








4 Answers
4






active

oldest

votes









active

oldest

votes






active

oldest

votes









8












$begingroup$

The neutral wire is defined to be 0V. And each phase individually has a voltage relative to neutral of 115V if you are in the US, and 230V if you are in most of Europe.



But because the three phases are 120 deg out of phase compared to each other this results in a voltage difference of 115V * sqrt(3) = 200V (or 230V * sqrt(3) = 400V) between any two phases.



Depending on the type of mains distribution system you've got in the country you live (I don't know how it is in the US) the neutral wire might be connected to earth at the power company. Keep in mind however, that even though the neutral wire might be connected to earth, this doesn't mean that it is actually at earth potential, because a return current might be flowing in the neutral wire, and due to the resistance in the wire this will cause a voltage at your end of the neutral wire.



It is also important to keep in mind that in many countries the mains plugs we use can actually be turned 180 deg putting line where neutral was supposed to be, meaning that with these kinds of systems you can never be sure if your neutral is actually neutral or line (BE CAREFUL!)



So to sum it up: The neutral wire is defined to be 0V. But will typically be at some voltage potential (relative to earth).






share|improve this answer









$endgroup$








  • 1




    $begingroup$
    Sometimes, earth is defined to be zero volts instead of neutral. Though they're nominally the same, they can differ. This can be important, and I feel like it ought to be mentioned at least.
    $endgroup$
    – Hearth
    May 5 at 16:21
















8












$begingroup$

The neutral wire is defined to be 0V. And each phase individually has a voltage relative to neutral of 115V if you are in the US, and 230V if you are in most of Europe.



But because the three phases are 120 deg out of phase compared to each other this results in a voltage difference of 115V * sqrt(3) = 200V (or 230V * sqrt(3) = 400V) between any two phases.



Depending on the type of mains distribution system you've got in the country you live (I don't know how it is in the US) the neutral wire might be connected to earth at the power company. Keep in mind however, that even though the neutral wire might be connected to earth, this doesn't mean that it is actually at earth potential, because a return current might be flowing in the neutral wire, and due to the resistance in the wire this will cause a voltage at your end of the neutral wire.



It is also important to keep in mind that in many countries the mains plugs we use can actually be turned 180 deg putting line where neutral was supposed to be, meaning that with these kinds of systems you can never be sure if your neutral is actually neutral or line (BE CAREFUL!)



So to sum it up: The neutral wire is defined to be 0V. But will typically be at some voltage potential (relative to earth).






share|improve this answer









$endgroup$








  • 1




    $begingroup$
    Sometimes, earth is defined to be zero volts instead of neutral. Though they're nominally the same, they can differ. This can be important, and I feel like it ought to be mentioned at least.
    $endgroup$
    – Hearth
    May 5 at 16:21














8












8








8





$begingroup$

The neutral wire is defined to be 0V. And each phase individually has a voltage relative to neutral of 115V if you are in the US, and 230V if you are in most of Europe.



But because the three phases are 120 deg out of phase compared to each other this results in a voltage difference of 115V * sqrt(3) = 200V (or 230V * sqrt(3) = 400V) between any two phases.



Depending on the type of mains distribution system you've got in the country you live (I don't know how it is in the US) the neutral wire might be connected to earth at the power company. Keep in mind however, that even though the neutral wire might be connected to earth, this doesn't mean that it is actually at earth potential, because a return current might be flowing in the neutral wire, and due to the resistance in the wire this will cause a voltage at your end of the neutral wire.



It is also important to keep in mind that in many countries the mains plugs we use can actually be turned 180 deg putting line where neutral was supposed to be, meaning that with these kinds of systems you can never be sure if your neutral is actually neutral or line (BE CAREFUL!)



So to sum it up: The neutral wire is defined to be 0V. But will typically be at some voltage potential (relative to earth).






share|improve this answer









$endgroup$



The neutral wire is defined to be 0V. And each phase individually has a voltage relative to neutral of 115V if you are in the US, and 230V if you are in most of Europe.



But because the three phases are 120 deg out of phase compared to each other this results in a voltage difference of 115V * sqrt(3) = 200V (or 230V * sqrt(3) = 400V) between any two phases.



Depending on the type of mains distribution system you've got in the country you live (I don't know how it is in the US) the neutral wire might be connected to earth at the power company. Keep in mind however, that even though the neutral wire might be connected to earth, this doesn't mean that it is actually at earth potential, because a return current might be flowing in the neutral wire, and due to the resistance in the wire this will cause a voltage at your end of the neutral wire.



It is also important to keep in mind that in many countries the mains plugs we use can actually be turned 180 deg putting line where neutral was supposed to be, meaning that with these kinds of systems you can never be sure if your neutral is actually neutral or line (BE CAREFUL!)



So to sum it up: The neutral wire is defined to be 0V. But will typically be at some voltage potential (relative to earth).







share|improve this answer












share|improve this answer



share|improve this answer










answered May 5 at 13:00









VinzentVinzent

75718




75718







  • 1




    $begingroup$
    Sometimes, earth is defined to be zero volts instead of neutral. Though they're nominally the same, they can differ. This can be important, and I feel like it ought to be mentioned at least.
    $endgroup$
    – Hearth
    May 5 at 16:21













  • 1




    $begingroup$
    Sometimes, earth is defined to be zero volts instead of neutral. Though they're nominally the same, they can differ. This can be important, and I feel like it ought to be mentioned at least.
    $endgroup$
    – Hearth
    May 5 at 16:21








1




1




$begingroup$
Sometimes, earth is defined to be zero volts instead of neutral. Though they're nominally the same, they can differ. This can be important, and I feel like it ought to be mentioned at least.
$endgroup$
– Hearth
May 5 at 16:21





$begingroup$
Sometimes, earth is defined to be zero volts instead of neutral. Though they're nominally the same, they can differ. This can be important, and I feel like it ought to be mentioned at least.
$endgroup$
– Hearth
May 5 at 16:21














9












$begingroup$

The original article you've quoted is garbled.




... the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact).




It can't be three times higher and $ sqrt 3$ times higher simultaneously. The correct value is $ sqrt 3$ times higher.



enter image description here



Figure 1. The diagram in question. Source: PacketPower.




When he says the X-N voltage is 120 V, with N being the reference voltage, is the reference voltage 0 V or does it have some value?




The reference is the wye (star) point where the three windings share a common node. In this diagram it is neutralised by connecting to Earth. (That means that this conductor should not see any significant voltage on it with respect to earth.) There will be 120 V between each of the phases and the wye point whether it is earthed or not.




From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?




It depends on local regulations. If we're dealing with a transformer secondary here then typically the primary will be delta powered so there may be no neutral on the incoming supply. The solution is to ground the wye to the building's earth bonding in which case it would be the same as earth grounding. In the case of a ship, for example, the "earth" would be the ship's hull.



enter image description here



Figure 2. A delta-wye (delta-star) transformer connection. Source: Gamatronic.



Here we can see that there is no neutral connection on the incoming supply. Using a wye configuration on the secondary allows us to create one for internal use. The wye point can be left floating or can be grounded.






share|improve this answer









$endgroup$












  • $begingroup$
    "Here we can see that there is no neutral connection on the incoming supply." So what provides the return path for flow of current?
    $endgroup$
    – noorav
    May 5 at 13:53











  • $begingroup$
    The other two phases. See my answer to How do remaining two phases act as return path in three phase system?
    $endgroup$
    – Transistor
    May 5 at 14:21















9












$begingroup$

The original article you've quoted is garbled.




... the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact).




It can't be three times higher and $ sqrt 3$ times higher simultaneously. The correct value is $ sqrt 3$ times higher.



enter image description here



Figure 1. The diagram in question. Source: PacketPower.




When he says the X-N voltage is 120 V, with N being the reference voltage, is the reference voltage 0 V or does it have some value?




The reference is the wye (star) point where the three windings share a common node. In this diagram it is neutralised by connecting to Earth. (That means that this conductor should not see any significant voltage on it with respect to earth.) There will be 120 V between each of the phases and the wye point whether it is earthed or not.




From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?




It depends on local regulations. If we're dealing with a transformer secondary here then typically the primary will be delta powered so there may be no neutral on the incoming supply. The solution is to ground the wye to the building's earth bonding in which case it would be the same as earth grounding. In the case of a ship, for example, the "earth" would be the ship's hull.



enter image description here



Figure 2. A delta-wye (delta-star) transformer connection. Source: Gamatronic.



Here we can see that there is no neutral connection on the incoming supply. Using a wye configuration on the secondary allows us to create one for internal use. The wye point can be left floating or can be grounded.






share|improve this answer









$endgroup$












  • $begingroup$
    "Here we can see that there is no neutral connection on the incoming supply." So what provides the return path for flow of current?
    $endgroup$
    – noorav
    May 5 at 13:53











  • $begingroup$
    The other two phases. See my answer to How do remaining two phases act as return path in three phase system?
    $endgroup$
    – Transistor
    May 5 at 14:21













9












9








9





$begingroup$

The original article you've quoted is garbled.




... the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact).




It can't be three times higher and $ sqrt 3$ times higher simultaneously. The correct value is $ sqrt 3$ times higher.



enter image description here



Figure 1. The diagram in question. Source: PacketPower.




When he says the X-N voltage is 120 V, with N being the reference voltage, is the reference voltage 0 V or does it have some value?




The reference is the wye (star) point where the three windings share a common node. In this diagram it is neutralised by connecting to Earth. (That means that this conductor should not see any significant voltage on it with respect to earth.) There will be 120 V between each of the phases and the wye point whether it is earthed or not.




From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?




It depends on local regulations. If we're dealing with a transformer secondary here then typically the primary will be delta powered so there may be no neutral on the incoming supply. The solution is to ground the wye to the building's earth bonding in which case it would be the same as earth grounding. In the case of a ship, for example, the "earth" would be the ship's hull.



enter image description here



Figure 2. A delta-wye (delta-star) transformer connection. Source: Gamatronic.



Here we can see that there is no neutral connection on the incoming supply. Using a wye configuration on the secondary allows us to create one for internal use. The wye point can be left floating or can be grounded.






share|improve this answer









$endgroup$



The original article you've quoted is garbled.




... the voltage between any two phases is 3 times higher than the voltage of an individual phase by a factor of 1.73 (square root of 3 to be exact).




It can't be three times higher and $ sqrt 3$ times higher simultaneously. The correct value is $ sqrt 3$ times higher.



enter image description here



Figure 1. The diagram in question. Source: PacketPower.




When he says the X-N voltage is 120 V, with N being the reference voltage, is the reference voltage 0 V or does it have some value?




The reference is the wye (star) point where the three windings share a common node. In this diagram it is neutralised by connecting to Earth. (That means that this conductor should not see any significant voltage on it with respect to earth.) There will be 120 V between each of the phases and the wye point whether it is earthed or not.




From the diagram (in the link,) I realise that the neutral wire is grounded, but is this the same as earth grounding? Doesn't the neutral wire go back to the transformer so as to provide a closed circuit?




It depends on local regulations. If we're dealing with a transformer secondary here then typically the primary will be delta powered so there may be no neutral on the incoming supply. The solution is to ground the wye to the building's earth bonding in which case it would be the same as earth grounding. In the case of a ship, for example, the "earth" would be the ship's hull.



enter image description here



Figure 2. A delta-wye (delta-star) transformer connection. Source: Gamatronic.



Here we can see that there is no neutral connection on the incoming supply. Using a wye configuration on the secondary allows us to create one for internal use. The wye point can be left floating or can be grounded.







share|improve this answer












share|improve this answer



share|improve this answer










answered May 5 at 13:02









TransistorTransistor

91.4k788195




91.4k788195











  • $begingroup$
    "Here we can see that there is no neutral connection on the incoming supply." So what provides the return path for flow of current?
    $endgroup$
    – noorav
    May 5 at 13:53











  • $begingroup$
    The other two phases. See my answer to How do remaining two phases act as return path in three phase system?
    $endgroup$
    – Transistor
    May 5 at 14:21
















  • $begingroup$
    "Here we can see that there is no neutral connection on the incoming supply." So what provides the return path for flow of current?
    $endgroup$
    – noorav
    May 5 at 13:53











  • $begingroup$
    The other two phases. See my answer to How do remaining two phases act as return path in three phase system?
    $endgroup$
    – Transistor
    May 5 at 14:21















$begingroup$
"Here we can see that there is no neutral connection on the incoming supply." So what provides the return path for flow of current?
$endgroup$
– noorav
May 5 at 13:53





$begingroup$
"Here we can see that there is no neutral connection on the incoming supply." So what provides the return path for flow of current?
$endgroup$
– noorav
May 5 at 13:53













$begingroup$
The other two phases. See my answer to How do remaining two phases act as return path in three phase system?
$endgroup$
– Transistor
May 5 at 14:21




$begingroup$
The other two phases. See my answer to How do remaining two phases act as return path in three phase system?
$endgroup$
– Transistor
May 5 at 14:21











1












$begingroup$

The neutral wire is grounded, so if you literally took a multi-meter and tried to read voltage between the neutral wire and ground, you will read 0 voltage. Please note, this is for a healthy working balanced system.



So yes, consider the neutral wire 0V if everything is in working order.






share|improve this answer









$endgroup$












  • $begingroup$
    That depends completely on the type of distribution system is used in the country you live in. In most of Europe the neutral is indeed connected to earth at the power company, but this is not always the case/ not the case in all countries..
    $endgroup$
    – Vinzent
    May 5 at 13:02










  • $begingroup$
    Do you have an example where someone is running power through the neutral wire? Would be interesting to see this setup.
    $endgroup$
    – Busta
    May 5 at 13:05






  • 1




    $begingroup$
    You can read this wiki page about earthing systems: en.wikipedia.org/wiki/Earthing_system, It describes the different types of earthing systems, such as TN, TT, IN and IT..
    $endgroup$
    – Vinzent
    May 5 at 13:10










  • $begingroup$
    Thanks for the link. So I will default that my answer works in traditional WYE (Star) / Delta systems that use a 4-wire 3-phase traditional set-up where the neutral is tied to the ground. Hence, if you tried to read voltage between neutral and ground...theoretically you should get 0volts but your answer explained why you may see some voltage.. The original question gave the assumption that the neutral wire is grounded.
    $endgroup$
    – Busta
    May 5 at 13:18
















1












$begingroup$

The neutral wire is grounded, so if you literally took a multi-meter and tried to read voltage between the neutral wire and ground, you will read 0 voltage. Please note, this is for a healthy working balanced system.



So yes, consider the neutral wire 0V if everything is in working order.






share|improve this answer









$endgroup$












  • $begingroup$
    That depends completely on the type of distribution system is used in the country you live in. In most of Europe the neutral is indeed connected to earth at the power company, but this is not always the case/ not the case in all countries..
    $endgroup$
    – Vinzent
    May 5 at 13:02










  • $begingroup$
    Do you have an example where someone is running power through the neutral wire? Would be interesting to see this setup.
    $endgroup$
    – Busta
    May 5 at 13:05






  • 1




    $begingroup$
    You can read this wiki page about earthing systems: en.wikipedia.org/wiki/Earthing_system, It describes the different types of earthing systems, such as TN, TT, IN and IT..
    $endgroup$
    – Vinzent
    May 5 at 13:10










  • $begingroup$
    Thanks for the link. So I will default that my answer works in traditional WYE (Star) / Delta systems that use a 4-wire 3-phase traditional set-up where the neutral is tied to the ground. Hence, if you tried to read voltage between neutral and ground...theoretically you should get 0volts but your answer explained why you may see some voltage.. The original question gave the assumption that the neutral wire is grounded.
    $endgroup$
    – Busta
    May 5 at 13:18














1












1








1





$begingroup$

The neutral wire is grounded, so if you literally took a multi-meter and tried to read voltage between the neutral wire and ground, you will read 0 voltage. Please note, this is for a healthy working balanced system.



So yes, consider the neutral wire 0V if everything is in working order.






share|improve this answer









$endgroup$



The neutral wire is grounded, so if you literally took a multi-meter and tried to read voltage between the neutral wire and ground, you will read 0 voltage. Please note, this is for a healthy working balanced system.



So yes, consider the neutral wire 0V if everything is in working order.







share|improve this answer












share|improve this answer



share|improve this answer










answered May 5 at 13:00









BustaBusta

206




206











  • $begingroup$
    That depends completely on the type of distribution system is used in the country you live in. In most of Europe the neutral is indeed connected to earth at the power company, but this is not always the case/ not the case in all countries..
    $endgroup$
    – Vinzent
    May 5 at 13:02










  • $begingroup$
    Do you have an example where someone is running power through the neutral wire? Would be interesting to see this setup.
    $endgroup$
    – Busta
    May 5 at 13:05






  • 1




    $begingroup$
    You can read this wiki page about earthing systems: en.wikipedia.org/wiki/Earthing_system, It describes the different types of earthing systems, such as TN, TT, IN and IT..
    $endgroup$
    – Vinzent
    May 5 at 13:10










  • $begingroup$
    Thanks for the link. So I will default that my answer works in traditional WYE (Star) / Delta systems that use a 4-wire 3-phase traditional set-up where the neutral is tied to the ground. Hence, if you tried to read voltage between neutral and ground...theoretically you should get 0volts but your answer explained why you may see some voltage.. The original question gave the assumption that the neutral wire is grounded.
    $endgroup$
    – Busta
    May 5 at 13:18

















  • $begingroup$
    That depends completely on the type of distribution system is used in the country you live in. In most of Europe the neutral is indeed connected to earth at the power company, but this is not always the case/ not the case in all countries..
    $endgroup$
    – Vinzent
    May 5 at 13:02










  • $begingroup$
    Do you have an example where someone is running power through the neutral wire? Would be interesting to see this setup.
    $endgroup$
    – Busta
    May 5 at 13:05






  • 1




    $begingroup$
    You can read this wiki page about earthing systems: en.wikipedia.org/wiki/Earthing_system, It describes the different types of earthing systems, such as TN, TT, IN and IT..
    $endgroup$
    – Vinzent
    May 5 at 13:10










  • $begingroup$
    Thanks for the link. So I will default that my answer works in traditional WYE (Star) / Delta systems that use a 4-wire 3-phase traditional set-up where the neutral is tied to the ground. Hence, if you tried to read voltage between neutral and ground...theoretically you should get 0volts but your answer explained why you may see some voltage.. The original question gave the assumption that the neutral wire is grounded.
    $endgroup$
    – Busta
    May 5 at 13:18
















$begingroup$
That depends completely on the type of distribution system is used in the country you live in. In most of Europe the neutral is indeed connected to earth at the power company, but this is not always the case/ not the case in all countries..
$endgroup$
– Vinzent
May 5 at 13:02




$begingroup$
That depends completely on the type of distribution system is used in the country you live in. In most of Europe the neutral is indeed connected to earth at the power company, but this is not always the case/ not the case in all countries..
$endgroup$
– Vinzent
May 5 at 13:02












$begingroup$
Do you have an example where someone is running power through the neutral wire? Would be interesting to see this setup.
$endgroup$
– Busta
May 5 at 13:05




$begingroup$
Do you have an example where someone is running power through the neutral wire? Would be interesting to see this setup.
$endgroup$
– Busta
May 5 at 13:05




1




1




$begingroup$
You can read this wiki page about earthing systems: en.wikipedia.org/wiki/Earthing_system, It describes the different types of earthing systems, such as TN, TT, IN and IT..
$endgroup$
– Vinzent
May 5 at 13:10




$begingroup$
You can read this wiki page about earthing systems: en.wikipedia.org/wiki/Earthing_system, It describes the different types of earthing systems, such as TN, TT, IN and IT..
$endgroup$
– Vinzent
May 5 at 13:10












$begingroup$
Thanks for the link. So I will default that my answer works in traditional WYE (Star) / Delta systems that use a 4-wire 3-phase traditional set-up where the neutral is tied to the ground. Hence, if you tried to read voltage between neutral and ground...theoretically you should get 0volts but your answer explained why you may see some voltage.. The original question gave the assumption that the neutral wire is grounded.
$endgroup$
– Busta
May 5 at 13:18





$begingroup$
Thanks for the link. So I will default that my answer works in traditional WYE (Star) / Delta systems that use a 4-wire 3-phase traditional set-up where the neutral is tied to the ground. Hence, if you tried to read voltage between neutral and ground...theoretically you should get 0volts but your answer explained why you may see some voltage.. The original question gave the assumption that the neutral wire is grounded.
$endgroup$
– Busta
May 5 at 13:18












0












$begingroup$


"Here we can see that there is no neutral connection on the incoming supply."



So what provides the return path for flow of current?




This was asked as a comment, but to answer it I need far more space than a comment allows.



With a simple two wire AC connection, the outgoing current on the hot wire is has the exact same absolute magnitude as the return current in the neutral wire, but they have opposite signs. In addition to this, the current is actually a sine wave.



Now, lets take three copies of this, but adjust the phase of two of the circuits so that all three are 120 degrees out of phase with respect to each other.



Next, lets replace the three neutral wires with one big wire three times the capacity. Up to this point, everything is working just fine.



However, lets now take a close look at the current flowing in the neutral wire. It'll be the sum of the three individual component flows, i.e. the sum of three sine waves, each 120 degrees out of phase with respect to the others.



If you either draw it out, or sum it up mathematically, those three sine waves always add up to zero, at any point in time. This in turn means that there's actually no current flowing in that huge return wire. So why not just remove it, and let the three hot wires carry on doing what they're doing.



In practice, this works well enough that we can transmit power over large distances without an explicit return wire. Due to imbalances in the loads, there will be some return current, but it's generally small enough that using Earth as a return is sufficient.






share|improve this answer











$endgroup$












  • $begingroup$
    Actually, you don't even need the earth as a return. A delta-star transformer (what is found in most cases where voltage is stepped down for final use) converts line-neutral loads to line-line loads. Any imbalance in loading simply shows up as an imbalance of phase currents, not also a neutral current.
    $endgroup$
    – Someone Somewhere
    May 6 at 0:10










  • $begingroup$
    Star systems typically use a neutral conductor capable of carrying the same current as the phase conductors (or slightly more due to harmonics). Going smaller is not advisable as it is entirely possible for one phase to be very heavily loaded while the others are light.
    $endgroup$
    – Someone Somewhere
    May 6 at 0:12















0












$begingroup$


"Here we can see that there is no neutral connection on the incoming supply."



So what provides the return path for flow of current?




This was asked as a comment, but to answer it I need far more space than a comment allows.



With a simple two wire AC connection, the outgoing current on the hot wire is has the exact same absolute magnitude as the return current in the neutral wire, but they have opposite signs. In addition to this, the current is actually a sine wave.



Now, lets take three copies of this, but adjust the phase of two of the circuits so that all three are 120 degrees out of phase with respect to each other.



Next, lets replace the three neutral wires with one big wire three times the capacity. Up to this point, everything is working just fine.



However, lets now take a close look at the current flowing in the neutral wire. It'll be the sum of the three individual component flows, i.e. the sum of three sine waves, each 120 degrees out of phase with respect to the others.



If you either draw it out, or sum it up mathematically, those three sine waves always add up to zero, at any point in time. This in turn means that there's actually no current flowing in that huge return wire. So why not just remove it, and let the three hot wires carry on doing what they're doing.



In practice, this works well enough that we can transmit power over large distances without an explicit return wire. Due to imbalances in the loads, there will be some return current, but it's generally small enough that using Earth as a return is sufficient.






share|improve this answer











$endgroup$












  • $begingroup$
    Actually, you don't even need the earth as a return. A delta-star transformer (what is found in most cases where voltage is stepped down for final use) converts line-neutral loads to line-line loads. Any imbalance in loading simply shows up as an imbalance of phase currents, not also a neutral current.
    $endgroup$
    – Someone Somewhere
    May 6 at 0:10










  • $begingroup$
    Star systems typically use a neutral conductor capable of carrying the same current as the phase conductors (or slightly more due to harmonics). Going smaller is not advisable as it is entirely possible for one phase to be very heavily loaded while the others are light.
    $endgroup$
    – Someone Somewhere
    May 6 at 0:12













0












0








0





$begingroup$


"Here we can see that there is no neutral connection on the incoming supply."



So what provides the return path for flow of current?




This was asked as a comment, but to answer it I need far more space than a comment allows.



With a simple two wire AC connection, the outgoing current on the hot wire is has the exact same absolute magnitude as the return current in the neutral wire, but they have opposite signs. In addition to this, the current is actually a sine wave.



Now, lets take three copies of this, but adjust the phase of two of the circuits so that all three are 120 degrees out of phase with respect to each other.



Next, lets replace the three neutral wires with one big wire three times the capacity. Up to this point, everything is working just fine.



However, lets now take a close look at the current flowing in the neutral wire. It'll be the sum of the three individual component flows, i.e. the sum of three sine waves, each 120 degrees out of phase with respect to the others.



If you either draw it out, or sum it up mathematically, those three sine waves always add up to zero, at any point in time. This in turn means that there's actually no current flowing in that huge return wire. So why not just remove it, and let the three hot wires carry on doing what they're doing.



In practice, this works well enough that we can transmit power over large distances without an explicit return wire. Due to imbalances in the loads, there will be some return current, but it's generally small enough that using Earth as a return is sufficient.






share|improve this answer











$endgroup$




"Here we can see that there is no neutral connection on the incoming supply."



So what provides the return path for flow of current?




This was asked as a comment, but to answer it I need far more space than a comment allows.



With a simple two wire AC connection, the outgoing current on the hot wire is has the exact same absolute magnitude as the return current in the neutral wire, but they have opposite signs. In addition to this, the current is actually a sine wave.



Now, lets take three copies of this, but adjust the phase of two of the circuits so that all three are 120 degrees out of phase with respect to each other.



Next, lets replace the three neutral wires with one big wire three times the capacity. Up to this point, everything is working just fine.



However, lets now take a close look at the current flowing in the neutral wire. It'll be the sum of the three individual component flows, i.e. the sum of three sine waves, each 120 degrees out of phase with respect to the others.



If you either draw it out, or sum it up mathematically, those three sine waves always add up to zero, at any point in time. This in turn means that there's actually no current flowing in that huge return wire. So why not just remove it, and let the three hot wires carry on doing what they're doing.



In practice, this works well enough that we can transmit power over large distances without an explicit return wire. Due to imbalances in the loads, there will be some return current, but it's generally small enough that using Earth as a return is sufficient.







share|improve this answer














share|improve this answer



share|improve this answer








edited May 5 at 21:33

























answered May 5 at 21:21









dgnuffdgnuff

1084




1084











  • $begingroup$
    Actually, you don't even need the earth as a return. A delta-star transformer (what is found in most cases where voltage is stepped down for final use) converts line-neutral loads to line-line loads. Any imbalance in loading simply shows up as an imbalance of phase currents, not also a neutral current.
    $endgroup$
    – Someone Somewhere
    May 6 at 0:10










  • $begingroup$
    Star systems typically use a neutral conductor capable of carrying the same current as the phase conductors (or slightly more due to harmonics). Going smaller is not advisable as it is entirely possible for one phase to be very heavily loaded while the others are light.
    $endgroup$
    – Someone Somewhere
    May 6 at 0:12
















  • $begingroup$
    Actually, you don't even need the earth as a return. A delta-star transformer (what is found in most cases where voltage is stepped down for final use) converts line-neutral loads to line-line loads. Any imbalance in loading simply shows up as an imbalance of phase currents, not also a neutral current.
    $endgroup$
    – Someone Somewhere
    May 6 at 0:10










  • $begingroup$
    Star systems typically use a neutral conductor capable of carrying the same current as the phase conductors (or slightly more due to harmonics). Going smaller is not advisable as it is entirely possible for one phase to be very heavily loaded while the others are light.
    $endgroup$
    – Someone Somewhere
    May 6 at 0:12















$begingroup$
Actually, you don't even need the earth as a return. A delta-star transformer (what is found in most cases where voltage is stepped down for final use) converts line-neutral loads to line-line loads. Any imbalance in loading simply shows up as an imbalance of phase currents, not also a neutral current.
$endgroup$
– Someone Somewhere
May 6 at 0:10




$begingroup$
Actually, you don't even need the earth as a return. A delta-star transformer (what is found in most cases where voltage is stepped down for final use) converts line-neutral loads to line-line loads. Any imbalance in loading simply shows up as an imbalance of phase currents, not also a neutral current.
$endgroup$
– Someone Somewhere
May 6 at 0:10












$begingroup$
Star systems typically use a neutral conductor capable of carrying the same current as the phase conductors (or slightly more due to harmonics). Going smaller is not advisable as it is entirely possible for one phase to be very heavily loaded while the others are light.
$endgroup$
– Someone Somewhere
May 6 at 0:12




$begingroup$
Star systems typically use a neutral conductor capable of carrying the same current as the phase conductors (or slightly more due to harmonics). Going smaller is not advisable as it is entirely possible for one phase to be very heavily loaded while the others are light.
$endgroup$
– Someone Somewhere
May 6 at 0:12

















draft saved

draft discarded
















































Thanks for contributing an answer to Electrical Engineering Stack Exchange!


  • Please be sure to answer the question. Provide details and share your research!

But avoid


  • Asking for help, clarification, or responding to other answers.

  • Making statements based on opinion; back them up with references or personal experience.

Use MathJax to format equations. MathJax reference.


To learn more, see our tips on writing great answers.




draft saved


draft discarded














StackExchange.ready(
function ()
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2felectronics.stackexchange.com%2fquestions%2f437005%2fdoes-the-neutral-wire-have-any-voltage%23new-answer', 'question_page');

);

Post as a guest















Required, but never shown





















































Required, but never shown














Required, but never shown












Required, but never shown







Required, but never shown

































Required, but never shown














Required, but never shown












Required, but never shown







Required, but never shown







Popular posts from this blog

Wikipedia:Vital articles Мазмуну Biography - Өмүр баян Philosophy and psychology - Философия жана психология Religion - Дин Social sciences - Коомдук илимдер Language and literature - Тил жана адабият Science - Илим Technology - Технология Arts and recreation - Искусство жана эс алуу History and geography - Тарых жана география Навигация менюсу

Bruxelas-Capital Índice Historia | Composición | Situación lingüística | Clima | Cidades irmandadas | Notas | Véxase tamén | Menú de navegacióneO uso das linguas en Bruxelas e a situación do neerlandés"Rexión de Bruxelas Capital"o orixinalSitio da rexiónPáxina de Bruselas no sitio da Oficina de Promoción Turística de Valonia e BruxelasMapa Interactivo da Rexión de Bruxelas-CapitaleeWorldCat332144929079854441105155190212ID28008674080552-90000 0001 0666 3698n94104302ID540940339365017018237

What should I write in an apology letter, since I have decided not to join a company after accepting an offer letterShould I keep looking after accepting a job offer?What should I do when I've been verbally told I would get an offer letter, but still haven't gotten one after 4 weeks?Do I accept an offer from a company that I am not likely to join?New job hasn't confirmed starting date and I want to give current employer as much notice as possibleHow should I address my manager in my resignation letter?HR delayed background verification, now jobless as resignedNo email communication after accepting a formal written offer. How should I phrase the call?What should I do if after receiving a verbal offer letter I am informed that my written job offer is put on hold due to some internal issues?Should I inform the current employer that I am about to resign within 1-2 weeks since I have signed the offer letter and waiting for visa?What company will do, if I send their offer letter to another company